Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Room operating modes 2013-06-17
The table below shows the effect of the Temporary Comfort mode on the effective room
operating mode of the room controller.
Existing effective
room op. mode
Temporary
Comfort mode
New effective room
operating mode
Comfort
0 = Not used
No effect
Precomfort
1 = Trigger
Comfort
Economy
1 = Trigger
Comfort during Temporary
Comfort mode
1)
Protection mode
1 = Trigger
Protection, no change
Key: 1 means: "changes to 1"
1) Comfort mode is operative for the pre-defined Temporary Comfort period (see
page 143). The room controller then reverts to Economy.
5.4.7 Effective room operating mode
PPS2
S
Central Local
1.
3.
S
DI
S
S
DI
3.
Controller
1.
3.
Prio
3.
S
S
For the building automation and control system the
resulting effective room operating mode is available to
the building automation and control system as follows:
Effective room operating mode (Output communication object)
Flags
Type Send heartbeat States
R
W
C
T
U
1 0 1 1 0 20.102
DPT_HVACMode
Yes
1 = Comfort
2 = Precomfort
3 = Economy
4 = Protection
The resultant Effective room operating mode is also available as 4 digital
communication objects:
Effective room operating mode Comfort (output communication object)
Effective room operating mode Precomfort (output communication object)
Effective room operating mode Economy (output communication object)
Effective room operating mode Protection (output communication object)
Flags
Type Send heartbeat States
R
W
C
T
U
1 0 1 1 0 1.001
DPT_Switch
Yes 0 = Off
1 = On