Operating Instructions

Table Of Contents
51/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Room operating modes 2013-06-17
5.4.5 Local control of room operating mode with a room unit
Room unit
PPS2
S
Central Local
1.
3.
S
DI
S
S
DI
3.
Controller
1.
3.
Prio
3.
S
S
The
/Auto button on the room unit can be used like an
occupancy button.
The room user can use it to switch the HVAC system
"on" or "off".
The room unit is connected to the PPS2 interface on the room controller.
It displays the effective room operating mode in a simplified form, and can also be used
to change it.
State Description
Auto
Effective room operating mode is Comfort
Reduced mode in the room, depending on the Priority 1 and 2
influences as well as the Room operating mode schedule:
The effective room operating mode is Precomfort, Economy or
Protection.
The change in the effective room operating mode is event-driven, the key factor
being the point at which the button on the room unit is pressed.
The Effective occupancy or Temporary Comfort mode (both Priority 3) can cause the
effective room operating mode to change again the last command always applies.
The table below shows the effect of the
/Auto button on the effective room operating
mode of the room controller.
Existing effective
room op. mode
Display on
room unit
Manual operation of
/Auto button
New effective room
operating mode
Comfort Auto Precomfort
If room operating mode
from time schedule
= Comfort or Precomfort
Economy
If room operating mode
from time schedule
= Economy
Precomfort
Auto
Comfort
Economy Auto Comfort during Temporary
Comfort period
1)
Protection mode
Auto
Protection mode, no change
Key: " Auto" means: "Changes to Auto"
1) Comfort mode is operative for the pre-defined Temporary Comfort period (see
page 143). The room controller then reverts to Economy.
Effective
room operating mode