Operating Instructions

Table Of Contents
39/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Room operating modes 2013-06-17
The presence detector is connected directly to a digital input on the room controller
(see page 142); alternatively an EIB/KNX presence detector connected to the EIB/KNX
bus may be used (see diagram below).
The two inputs are OR-linked: If one signals presence, presence applies.
Since EIB/KNX presence detectors are available from a variety of manufacturers, the
name of the S-mode output communication object varies accordingly.
Room controller RXB...
Presence detector input
EIB / KNX presence detector
10385Z07en
Presence detector on DI
OR
Presence detector output
Delay on / off Without delay
The following S-mode communication object is used to integrate a presence detector
connected to the bus:
Presence detector input (Input communication object)
Flags Type
Receive timeout
States
R
W
C
T
U
1 0 1 1 0 1.018
DPT_Occupancy
Yes 0 = Unoccupied
1 = Occupied
The state of the local presence detector on the digital input is mapped in the building
automation and control system via the following S-mode output communication object:
Presence detector output (Output communication object)
Flags
Type Send hearbeat
States
R
W
C
T
U
0 1 1 0 0 1.018
DPT_Occupancy
No
0 = Unoccupied
1 = Occupied
Master/slave applications:
Bindings are required in S-mode, in order to transmit the slave presence detector status
to the master.
Effective occupancy
S
Zentral Lokal
1.
2.
3.
S
DI
S
S
S
DI
S
3.
Controller
Prio
PPS2
3.
S
The output communication object Effective
occupancy shows the occupancy status of the room
(based on a combination of time schedule and
presence detector).
In the case of integration into a building automation
and control system, the data is mapped to the
following output communication object:
Presence detector
CO
Note