Building Technologies Room operating modes 2013-06-17
5.3 Determine the room operating mode
in Desigo (S-mode)
In S-mode, the effective room operating mode of the room controller depends on the
central Use and Occupancy time schedules and/or on local influences such as window
contacts, presence detectors or a room unit.
The diagram below shows the priority of these influences and how they are processed
by the room controller:
10385Z55
PPS2
S
Presence detector
Room unit
Occupancy
Building use
Window contact
Central Local
1.
2.
3.
S
DI
S
S
S
DI
Effective
room op.
mode
S
Effective
occupancy
3.
Controller
Prio
Temporary
Comfort
mode
3.
S
The effects of Priority 1 and Priority 2 are similar in nature to continuous states
The Priority 3 influences are treated as events.
The key factor is the moment at which the state changes (trigger edge).
If the mode is later changed by another source of priority 3, the last change
applies.
STOP
Note!