Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Select communication mode 2013-06-17
The zones are defined under Communication.
Individual zones can also be disabled via "Command" if they are not being used. This
has the advantage of reducing the load on the bus.
HandyTool See Parameters in the last column of the table below
Short description
Basic setting
Parameter
Geographical zone (apartment)
– 1 (out of service)
*008
Geographical zone (room) 1 *009
Geographical zone (subzone)
1
*010
Time switch zone (apartment)
1
*011
Time switch zone (room)
1
*012
Time switch zone (subzone)
1
*013
Heat distr zone heating coil
1 (out of service)
*014
Heat distr zone cooling coil
1 (out of service)
*015
Heat distr zone heating surface
1 (out of service)
*016
Outside temperature zone
1
*018
Value 0 means broadcast and is therefore prohibited.
If in the Geogr. zone or in the Time switch zone one of the values is = 1, the entire
zone is "Out of service".
ACS Professional
Reducing the bus load
Notes