Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Select communication mode 2013-06-17
3 Select communication mode
As stated in section 1, the RXB Konnex room controllers operate either in S-mode or
LTE mode. They are used in S-mode when networked with the Desigo building
automation and control system, and in LTE mode with the Synco system.
The factory setting of all controllers and the basic setting of the tools is 0 = S-Mode.
This minimizes the bus load.
Exception: ACS changes the setting immediately to 1 = LTE + S.
The ETS Professional is used in Desigo networks.
It can be used for operation in
S-mode
LTE-mode and S-mode
Send heartbeat and Receive timeout are described in Section 11.1.
In a Synco network the ACS tool is used.
This has access to LTE mode only.
HandyTool
Setting Mode
*006 communication mode
0
S-Mode
1
LTE- and S-Mode
Note
ETS Professional
ACS