Operating Instructions

Table Of Contents
19/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Definitions / Tools 2013-06-17
If 4 or 5 is displayed, this mode can be selected via < (Enter).
The storage number (c1) is displayed and can be changed via + / . Select the desired
storage (1...5) via < (Enter).
If storage is empty, upload begins and the display flashes.
OK is displayed after successful upload.
If the storage is full, "dEL" for "Delete?" is displayed.
Pressing <(Enter) at this time overwrites the existing set.
If you press > (Escape), the storage number which you can change via + / is
displayed.
If the parameter set does not match the connected controller, error
message "Err" is displayed.
Press > (Escape) to return to the storage number and select a different number.
If the parameter set matches the connected controller, start download (display
flashes).
If connected successfully, "P1" is displayed (see 2.5.2).
2.7 Test the periphery using room unit QAX34.3
This function requires a QAX34.3 with index D or higher!
The HandyTool allows you to test the connected field devices (sensors, actuators).
This works only for the controller with the connected HandyTool; it does not work in
master/slave mode.
An application must be selected and fully parameterized in the controller
(address and zones can contain default values).
Start parameterization mode:
Press buttons < , > and simultaneously for about 2 s until the display turns dark.
Release the buttons.
Press button twice briefly.
Press buttons + and simultaneously for approx. 2s The display goes dark.
Press button + twice briefly.
The display now shows
0 (mode 0).
Use + and / or to choose between the following modes:
0 = Normal mode (normal room unit functions).
1 = Test mode
2 = Display mode (see 2.5.2).
3 = Parameterization mode (see 2.5.2
4 = Upload (see 2.6).
5 = Download (see 2.6).
6 = Service mode.
The following positions can be selected depending on the type of parameterization.
They are displayed with prefix "T".
The list shows all theoretically possible positions. However, only positions that are
available for selection based on the type of parameterization are displayed.
Uploading
Download
Prerequisite