Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Definitions / Tools 2013-06-17
+/allows for finding the number and pressing < (Enter) confirms it.
The corresponding value is displayed.
+/– allows for modifying the value and pressing < (Enter) confirms it.
> (Escape) returns to list without changing anything.
Pressing Escape one more time opens the list with the modes.
Pressing Escape a third time returns to the normal mode (room unit).
The parameter numbers are located in sections 13.6 and 13.7 as well as in the sections
where the functions are described.
A table of parameters with enumerations for the HandyTool is shown in Section 13.8.
2.5.4 Selection of the device address using room unit
QAX34.3
The device address is defined in parameters *001, *002 and *003.
*001 can be set to a value in the range 0...15
*002 can be set to a value in the range 0...15
*003 can be set to a value in the range 1...255
e.g. 0.2.27
Each address may occur once only in a given plant.
2.6 Upload/download parameters using room
unit QAX34.3
This function requires a QAX34.3 with index D or higher!
The HandyTool can save 5 different controller parameter sets.
These are uploaded from a fully parameterized controller using the Upload function.
Download allows for transferring such a data set to one or several controllers
(prerequisite: same controller type).
The address, and for LTE, the zones must be adjusted (see 2.5.2).
Download allows for changing also critical values.
As a worst case scenario, components (controllers/actuators or other plant
parts) may be destroyed.
Start parameterization mode:
Press buttons < , > and simultaneously for about 2 s until the display turns dark.
Release the buttons.
Press button twice briefly.
Press buttons + and simultaneously for approx. 2s The display goes dark.
Press button + twice briefly.
The display now shows
0 (mode 0).
Use + and / or to choose between the following modes:
0 = Normal mode (normal room unit functions).
1 = Test mode (see 2.7).
2 = Display mode (see 2.5.2).
3 = Parameterization mode (see 2.5.2 ).
4 = Uploading
5 = Download
6 = Service mode.
Note
STOP
Caution!