Operating Instructions

Table Of Contents
178/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Integrate RXB in Desigo/Synco 2013-06-17
15.4 Case 4: Display in Desigo/Synco,
with shared Synco time scheduler
Communication:
between controllers LTE mode via zones
with Desigo: Individual addressing or S-Mode
with ACS: Individual addressing
RXB display: Desigo and ACS
Synco display: Desigo and ACS
RXB time scheduler: from Synco
Energy demand: to Synco
The Desigo time scheduler must be disabled by a specialist.
In theory simultaneous display via Desigo and Synco is possible. However,
problems do arise with the manipulation of values (heartbeat, “last one rules”)
Geographical zone
Geographical zone
Geographical zone
Timeswitch zone
Heating demand zone
Cooling demand zone
10385D65
PXC... PXC... PX KNX
RXB
RXB
RXB
DESIGO
INSIGHT
ALN
FLN
Konnex
Individual addressing
PXM20
Synco Synco Synco
ACS7...
STOP
Important note