Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- RXB Description of functions for FC10, FC11, FC12, FC13
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communication mode
- 4 Applications, parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode in Desigo (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use time schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode viathe Room operating mode time schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 Desigo examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via the window contact input
- 5.4.2 Central control of room operating mode via the Room operating mode time schedule
- 5.4.3 Central control of room operating mode via the Use and Occupancy time schedules
- 5.4.4 Central and local control of room operating modebased on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via the window contact input
- 5.5.2 Central control of the room operating mode via Enable Comfort
- 5.5.3 Central control of room operating mode via Room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE-Mode Examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Fan control
- 10 Master/slave
- 11 General and central functions
- 11.1 Send heartbeat and receive timeouts
- 11.2 Digital inputs
- 11.3 Temporary Comfort mode
- 11.4 Presence detector switch-on and switchoff delay
- 11.5 Heating and cooling demand
- 11.6 Heating/cooling signal output
- 11.7 Special functions
- 11.8 Boost heating (Morning Warmup, 2)
- 11.9 Night purge (Night Purge, 4), (FNC10, FNC12)
- 11.10 Precooling (Precool, 5)
- 11.11 Test mode (Test, 7)
- 11.12 Emergency heating (Emergency Heat, 8)
- 11.13 Rapid ventilation (Fan only, 9)
- 11.14 Free cooling (Freecool, 10)
- 11.15 Alarm
- 11.16 Reset the setpoint shift
- 11.17 Free inputs/outputs
- 11.18 Software version
- 11.19 Device state
- 12 Room unit
- 13 KNX information
- 14 FAQs
- 15 Integrate RXB in Desigo/Synco
- 15.1 Case 1: Integration into Synco
- 15.2 Case 2: Integration into Desigo
- 15.3 Case 3: Display in Desigo, with shared Synco time scheduler
- 15.4 Case 4: Display in Desigo/Synco, with shared Synco time scheduler
- 15.5 Case 5: Display in Desigo, andseparate time schedulers
- 15.6 Case 6: Separate display, andseparate time schedulers
- 15.7 Case 7: Separate display, andshared Synco time scheduler
- 16 Working with different tools
171/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies KNX information 2013-06-17
13.9 Data point type description
Instead of the previously referenced EIS data types, this document now makes
reference to the new Konnex data point types.
Where possible, the tables which follow do include a reference to the corresponding
EIS type.
Data point types
ID
Name
Format
Unit
Range/Coding
Corresp. to EIS
1.001 DPT_Switch B
(1)
Bit 0 = OFF
1 = ON
EIS1
1.003 DPT_Enable B
(1)
Bit 0 = Disabled
1 = Enabled
EIS1
1.005 DPT_Alarm B
(1)
Bit 0 = No alarm
1 = Alarm
EIS1
1.017 DPT_Trigger B
(1)
Bit 0 = (not used)
1 = Trigger
EIS1
1.018 DPT_Occupancy B
(1)
Bit 0 = Unoccupied
1 = Occupied
EIS1
1.019 DPT_Window_Door B
(1)
Bit 0 = Closed
1 = Open
EIS1
1.100 DPT_HeatCool B
(1)
Bit 0 = Cooling
1 = Heating
EIS1
5.001 DPT_Scaling U
(8)
% 0...100% 0 = 0%
255 = 100%
EIS6
5.004 DPT_RelPosValve U
(8)
% 0...100% 0 = 0%
255 = 255%
EIS6
6.001 DPT_Percent_V8 V
(8)
% -100%...+100% -100 = -100%
+100 =+100%
(EIS14)
8.010 DPT_Percent_V16 V
(16)
% -100%...+100% -10000 = -100%
0 = 0%
+10000 =+100%
EIS10
9.001
DPT_Value_Temp
F
(16)
°C
Floating point
EIS5
9.002 DPT_Value_Tempd F
(16)
K Floating point EIS5
9.024
DPT_Value_Tempd
F
(16)
kW
Floating Point
EIS5
20.002
DPT_BuildingMode
N
(8)
Enum.
0 = In use
1 = Not in use
2 = Protection
(EIS14)
20.003 DPT_OccMode N
(8)
Enum. 0 = Occupied
1 = Standby
2 = Unoccupied
(EIS14)
20.102 DPT_HVACMode N
(8)
Enum. 0 = Auto
1 = Comfort
2 = Precomfort
3 = Economy
4 = Protection
(EIS14)
20.105 DPT_HVACContr
Mode
N
(8)
Enum. 0 = Auto
1 = Heat
2 = Morning Warmup
3 = Cool
4 = Night Purge
5 = Precool
6 = Off
7 = Test
8 = Emergency Heat
9 = Fan only
10 = Free Cool
11 = Ice
20 = noDem
255 = NUL
Other: Reserved
(EIS14)