Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- RXB Description of functions for FC10, FC11, FC12, FC13
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communication mode
- 4 Applications, parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode in Desigo (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use time schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode viathe Room operating mode time schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 Desigo examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via the window contact input
- 5.4.2 Central control of room operating mode via the Room operating mode time schedule
- 5.4.3 Central control of room operating mode via the Use and Occupancy time schedules
- 5.4.4 Central and local control of room operating modebased on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via the window contact input
- 5.5.2 Central control of the room operating mode via Enable Comfort
- 5.5.3 Central control of room operating mode via Room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE-Mode Examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Fan control
- 10 Master/slave
- 11 General and central functions
- 11.1 Send heartbeat and receive timeouts
- 11.2 Digital inputs
- 11.3 Temporary Comfort mode
- 11.4 Presence detector switch-on and switchoff delay
- 11.5 Heating and cooling demand
- 11.6 Heating/cooling signal output
- 11.7 Special functions
- 11.8 Boost heating (Morning Warmup, 2)
- 11.9 Night purge (Night Purge, 4), (FNC10, FNC12)
- 11.10 Precooling (Precool, 5)
- 11.11 Test mode (Test, 7)
- 11.12 Emergency heating (Emergency Heat, 8)
- 11.13 Rapid ventilation (Fan only, 9)
- 11.14 Free cooling (Freecool, 10)
- 11.15 Alarm
- 11.16 Reset the setpoint shift
- 11.17 Free inputs/outputs
- 11.18 Software version
- 11.19 Device state
- 12 Room unit
- 13 KNX information
- 14 FAQs
- 15 Integrate RXB in Desigo/Synco
- 15.1 Case 1: Integration into Synco
- 15.2 Case 2: Integration into Desigo
- 15.3 Case 3: Display in Desigo, with shared Synco time scheduler
- 15.4 Case 4: Display in Desigo/Synco, with shared Synco time scheduler
- 15.5 Case 5: Display in Desigo, andseparate time schedulers
- 15.6 Case 6: Separate display, andseparate time schedulers
- 15.7 Case 7: Separate display, andshared Synco time scheduler
- 16 Working with different tools
170/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies KNX information 2013-06-17
13.8 HandyTool enumerations
No. Parameter
CLC / RAD
FNC
1 - 3
Physical address X X
5 Plant type X X
FC-10 FC-11 FC-12 FC-13
6 Communications mode. X X
0 = S-Mode 1 = FNC02 1 = FNC10 1 = FNC03 1 = FNC02
8 - 10 Geographical zone X X
1 = S+LTE-M 2 = FNC04 2 = FNC12 2 = FNC05 2 = FNC03
11 -13 Time switch zone X X
3 = FNC08 3 = FNC18 3 = FNC04
14
Heat distribution zone air heater. X
4 = FNC20 4 = FNC08
15 Refrig distribution zone air cooler. X
CC-02
16 Heat distr zone heating surface X X
1 = CLC01
17 Refrig distr zone cooling surface X
2 = CLC02
18 Outside temperature zone X X
3 = RAD01
21
Master/slave. X X
0 = Slave
22 - 24 Master/slave zone X X
1 = Master
30 - 37 Setpoints X X
C: Prot / Eco / Pre-C / Comf H: Comf / Pre-C / Eco / Prot
38 Minimum supply air temperature X
39 Maximum supply air temperature X
40
Risk of frost limit X
50 Control sequence X
0 = c/o / 1 = Cooling / 2 = Heating
51
Actuator type cool surf valve
X
VA VA = Valve actuators:
52
Running time cool surface valve
X
54
Offset cooling surface valve
X
1 = STE71 10 = SSA81 250 = Mot BUS
56
Electric heater X
1 = on/off 3 = STA71 11 = SSB81 252 = El-mech 3rd
57 Power consumption el heater X
254 = continuous 4 = STP71 12 = SQS81 253 = Therm. 3rd
58 Positioning sign max el heater X
5 = STA72E 13 = SSC81 254 = Mot. 3rd
59 Positioning sign min el heater X
6 = STP72E 14 = SSP 81
60 Actuator type H/C coil valve X
VA
61
Running time damper heating X
62 Running time damper cooling X
63 Actuator type heat surf valve X X
VA
64 Running time heat surface valve X X
66 Offset heating surface valve X X
68
Position signal max valve actuator X
69 Position signal min valve actuator X
70 Changeover time damper X
71 Offset heating valve X
72
Offset cooling valve X
73 Outside temp min damper pos X
74 Running time outside air damper X
75 Minimum damper position X
78 Outside temp 0% valve pos X X
79
Outside temp max valve pos X X
80 Max valve position X
85 Heating (coil) outp bus valve X
86 Heating surface output bus valve actuator X
0 = OFF
87 Cooling (coil) outp bus valve X
1 = ON
88
Cooling surface outp bus valve, X
89 Heating outp bus el heating X
92 Temperature sensor. X X
0 = Ret. air / 1 = Room / 3 = Meas. val. / 255 = No sensor
93 Fan control X
0 = manual / 1 = automatic
94 Fan speeds X
0 = automatic / 1 = 1-stage / 2 = 2-stage / 3 = 3-stage
95
Minimum on time X
96 Periodic fan kick Comfort X
97 Periodic fan kick Eco X
98 Fan overrun time X
99 Enable electro heat relay
0 = disabled / 1 = enabled
101
Measured value correction X X
103 Setpoint offset range X X
105 Local Comfort mode X X
0 = disabled / 1 = enabled
108 Temperature unit X X
0 = °F / 1 = °C
109 Standard display X X
2 = Room temp. / 48 = Setpoint / 96 = No display
110
Setpoint display X X
0 = relative / 4 = absolute
113, 114 Digital input 1 / 2 X X
0 = Free: Bus=1 / Contact closed
115, 116 Digital input 3 / 4 X
1 = Free: Bus=1 / Contact open
117 Temporary Comfort mode X X
2 = Occupied / Contact closed
119 On-delay occupancy detector X X
3 = Occupied / Contact open
120
Off-delay occupancy detector X X
4 = Window open / Contact open
127 Send heartbeat X X
5 = Window open / Contact closed
128 Receive timeout X X
8 = Dewpoint. / Contact closed
131 Heat demand signal X X
9 = Dewppoint / Contact open
132 Cooling demand signal X X
0 = OFF 16 = Overtemp. / Contact open
134
Boost heating X X
1 = ON 17 = Overtemp. / Contact closed
135 Preecooling / Free cooling X X
32 = Frost / Contact closed
136 Rapid ventilation (earlier: air purge) X
33 = Frost / Contact open
137 Reset setpoint offset X X
34 = No air flow / Contact closed
138 Night purge X
35 = No air flow / Contact open
150, 151 Positioning signal fan max / min X
152, 153 Fan speed Heating max / min X
154, 155 Fan speed Cooling max / min X
156-158 Fan speed Precomf / Eco / Protection .min X
159 Fan overrun speed min X
160, 161 Fan start Heating / Cooling demand X
162, 163 Offset fan Heating / Cooling X
164, 165 P-band Xp fan Heatin / Cooling X
166, 167 Tn fan Heatin / Cooling X
168 Fan function Standby X
0 = disabled / 1 = enabled
169 Fan speed user defined X
0 = disabled / 1 = enabled
170-172 User fan speed 3 / 2 / 1 X
173 Enable fan relay X
0 = disabled / 1 = enabled
236
Application set
X X
237
Application version
X X
238
Operating system version
X X
239
KNX interface version
X X
240
Device state
X X