Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- RXB Description of functions for FC10, FC11, FC12, FC13
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communication mode
- 4 Applications, parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode in Desigo (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use time schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode viathe Room operating mode time schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 Desigo examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via the window contact input
- 5.4.2 Central control of room operating mode via the Room operating mode time schedule
- 5.4.3 Central control of room operating mode via the Use and Occupancy time schedules
- 5.4.4 Central and local control of room operating modebased on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via the window contact input
- 5.5.2 Central control of the room operating mode via Enable Comfort
- 5.5.3 Central control of room operating mode via Room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE-Mode Examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Fan control
- 10 Master/slave
- 11 General and central functions
- 11.1 Send heartbeat and receive timeouts
- 11.2 Digital inputs
- 11.3 Temporary Comfort mode
- 11.4 Presence detector switch-on and switchoff delay
- 11.5 Heating and cooling demand
- 11.6 Heating/cooling signal output
- 11.7 Special functions
- 11.8 Boost heating (Morning Warmup, 2)
- 11.9 Night purge (Night Purge, 4), (FNC10, FNC12)
- 11.10 Precooling (Precool, 5)
- 11.11 Test mode (Test, 7)
- 11.12 Emergency heating (Emergency Heat, 8)
- 11.13 Rapid ventilation (Fan only, 9)
- 11.14 Free cooling (Freecool, 10)
- 11.15 Alarm
- 11.16 Reset the setpoint shift
- 11.17 Free inputs/outputs
- 11.18 Software version
- 11.19 Device state
- 12 Room unit
- 13 KNX information
- 14 FAQs
- 15 Integrate RXB in Desigo/Synco
- 15.1 Case 1: Integration into Synco
- 15.2 Case 2: Integration into Desigo
- 15.3 Case 3: Display in Desigo, with shared Synco time scheduler
- 15.4 Case 4: Display in Desigo/Synco, with shared Synco time scheduler
- 15.5 Case 5: Display in Desigo, andseparate time schedulers
- 15.6 Case 6: Separate display, andseparate time schedulers
- 15.7 Case 7: Separate display, andshared Synco time scheduler
- 16 Working with different tools
17/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Definitions / Tools 2013-06-17
P001 Physical address (Area)
P002 Physical address (Line)
P003 Physical address (Device address)
P008 Geographical zone (Apartment) (if LTE is preset)
P009 Geographical zone (Room) (if LTE is preset)
P010 Geographical zone (Subzone) (if LTE is preset)
P011 Timeswitch zone (Apartment) (if LTE is preset)
P012 Timeswitch zone (Room) (if LTE is preset)
P013 Timeswitch zone (Subzone) (if LTE is preset)
P014 Heat distr. zone heating coil (if LTE is preset)
P015 Refr. distr. zone cooling coil (if LTE is preset)
P016 Heat distr. zone heating surface (if LTE is preset)
P018 Outside air temp zone (if LTE is preset)
P021 Master/Slave
P023 Master/Slave zone (group) (if LTE is preset)
P030 Protection cooling setpoint
P031 Economy cooling setpoint
P032 Precomfort cooling setpoint
P033 Comfort cooling setpoint
P034 Comfort heating setpoint
P035 Precomfort heating setpoint
P036 Economy heating setpoint
P037 Protection heating setpoint
P038 Min supply air temperature
P039 Max supply air temperature
P240 Device state
2.5.3 "Extended" parameter setting using room unit QAX34.3
This parameter setting also allows for adjusting critical values.
In the worst case, this may destroy a device (controller / fan coil / actuators or
other plant parts).
Start parameter setting mode
• Press buttons < , > and – simultaneously for 2 s until the display goes dark
• Release buttons
• Press – two times shortly
• Press + and – simultaneously for approx. 2s display goes dark
• Press + two times shortly
0 for Mode 0 is now displayed.
Use buttons + and / or – to select between the following modes:
•
0 = Normal mode (normal room unit functions)
•
1 = Test mode (see 2.7)
•
2 = Display mode: (see 2.5.2)
•
3 = Parameter mode: (see 2.5.2)
•
4 = Upload (see 2.6)
•
5 = Download (see 2.6)
•
6 = Service mode:
All parameters can be set. They are displayed with prefix "S".
Adjustable parameters
(Parameter mode)
STOP