Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- RXB Description of functions for FC10, FC11, FC12, FC13
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communication mode
- 4 Applications, parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode in Desigo (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use time schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode viathe Room operating mode time schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 Desigo examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via the window contact input
- 5.4.2 Central control of room operating mode via the Room operating mode time schedule
- 5.4.3 Central control of room operating mode via the Use and Occupancy time schedules
- 5.4.4 Central and local control of room operating modebased on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via the window contact input
- 5.5.2 Central control of the room operating mode via Enable Comfort
- 5.5.3 Central control of room operating mode via Room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE-Mode Examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Fan control
- 10 Master/slave
- 11 General and central functions
- 11.1 Send heartbeat and receive timeouts
- 11.2 Digital inputs
- 11.3 Temporary Comfort mode
- 11.4 Presence detector switch-on and switchoff delay
- 11.5 Heating and cooling demand
- 11.6 Heating/cooling signal output
- 11.7 Special functions
- 11.8 Boost heating (Morning Warmup, 2)
- 11.9 Night purge (Night Purge, 4), (FNC10, FNC12)
- 11.10 Precooling (Precool, 5)
- 11.11 Test mode (Test, 7)
- 11.12 Emergency heating (Emergency Heat, 8)
- 11.13 Rapid ventilation (Fan only, 9)
- 11.14 Free cooling (Freecool, 10)
- 11.15 Alarm
- 11.16 Reset the setpoint shift
- 11.17 Free inputs/outputs
- 11.18 Software version
- 11.19 Device state
- 12 Room unit
- 13 KNX information
- 14 FAQs
- 15 Integrate RXB in Desigo/Synco
- 15.1 Case 1: Integration into Synco
- 15.2 Case 2: Integration into Desigo
- 15.3 Case 3: Display in Desigo, with shared Synco time scheduler
- 15.4 Case 4: Display in Desigo/Synco, with shared Synco time scheduler
- 15.5 Case 5: Display in Desigo, andseparate time schedulers
- 15.6 Case 6: Separate display, andseparate time schedulers
- 15.7 Case 7: Separate display, andshared Synco time scheduler
- 16 Working with different tools
166/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies KNX information 2013-06-17
Visible FC-10 FC-11 FC-12 FC-13
Parameter No.
Description see page
Name
d = Display (display only)
(Mode 2)
P = Parameter (Mode 3)
("Lim param. setting"
)
S = Service (Mode 6)
("Ext. param. setting")
FNC02
FNC04
FNC08
FNC20
FNC10
FNC12
FNC18
FNC03
FNC05
FNC02
FNC03
FNC04
FNC08
151
130
Positioning signal min fan
d
S
X
X
X
X
152
130
Fan speed heating max
d
S
X
X
X
X
153
130
Fan speed heating min
d
S
X
X
X
X
154
130
Fan speed cooling max
d
S
X
X
X
X
155
130
Fan speed cooling min
d
S
X
X
X
X
156
130
Fan speed Precomfort min
d
S
X
X
X
X
157
130
Fan speed Economy min
d
S
X
X
X
X
158
130
Fan speed Protection min
d
S
X
X
X
X
159
131
Fan overrun speed min
d
S
X
160
123,
130
Fan start heating demand
d
S
X
X
X
161
123,
130
Fan start cooling demand
d
S
X
X
X
162
130
Offset heating fan
d
S
X
X
X
163
130
Offset cooling fan
d
S
X
X
X
164
130
P-band Xp heating fan
d
S
X
X
X
165
130
P-band Xp cooling fan
d
S
X
X
X
166
130
Tn heating fan
d
S
X
X
X
167
130
Tn cooling fan
d
S
X
X
X
168
126,
159
Fan function standby
d
S
X
X
X
X
169
159
Fan speed user defined
d
S
X
X
X
X
170
159
User fan speed 3
d
S
X
X
X
X
171
159
User fan speed 2
d
S
X
X
X
X
172
159
User fan speed 1
d
S
X
X
X
X
173
159
Enable fan relay
d
S
X
X
X
X
236
155
Application set
d
S
X
X
X
X
X
X
X
X
X
X
X
X
X
237
155
Application version
d
S
X
X
X
X
X
X
X
X
X
X
X
X
X
238
155
Operating system version
d
S
X
X
X
X
X
X
X
X
X
X
X
X
X
239
155
KNX interface version
d
S
X
X
X
X
X
X
X
X
X
X
X
X
X
240
155
Device state
d
P
S
X
X
X
X
X
X
X
X
X
X
X
X
X
1) HandyTool: In FNC20, runtime damper heating
2) HandyTool: In FNC20, runtime damper cooling
5) HandyTool: In FNC20, output bus damper actuator
7) HandyTool: Cannot be mapped
8) HandyTool: Visible, but not used by application
9) FNC08: always Supply air