Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- RXB Description of functions for FC10, FC11, FC12, FC13
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communication mode
- 4 Applications, parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode in Desigo (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use time schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode viathe Room operating mode time schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 Desigo examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via the window contact input
- 5.4.2 Central control of room operating mode via the Room operating mode time schedule
- 5.4.3 Central control of room operating mode via the Use and Occupancy time schedules
- 5.4.4 Central and local control of room operating modebased on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via the window contact input
- 5.5.2 Central control of the room operating mode via Enable Comfort
- 5.5.3 Central control of room operating mode via Room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE-Mode Examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Fan control
- 10 Master/slave
- 11 General and central functions
- 11.1 Send heartbeat and receive timeouts
- 11.2 Digital inputs
- 11.3 Temporary Comfort mode
- 11.4 Presence detector switch-on and switchoff delay
- 11.5 Heating and cooling demand
- 11.6 Heating/cooling signal output
- 11.7 Special functions
- 11.8 Boost heating (Morning Warmup, 2)
- 11.9 Night purge (Night Purge, 4), (FNC10, FNC12)
- 11.10 Precooling (Precool, 5)
- 11.11 Test mode (Test, 7)
- 11.12 Emergency heating (Emergency Heat, 8)
- 11.13 Rapid ventilation (Fan only, 9)
- 11.14 Free cooling (Freecool, 10)
- 11.15 Alarm
- 11.16 Reset the setpoint shift
- 11.17 Free inputs/outputs
- 11.18 Software version
- 11.19 Device state
- 12 Room unit
- 13 KNX information
- 14 FAQs
- 15 Integrate RXB in Desigo/Synco
- 15.1 Case 1: Integration into Synco
- 15.2 Case 2: Integration into Desigo
- 15.3 Case 3: Display in Desigo, with shared Synco time scheduler
- 15.4 Case 4: Display in Desigo/Synco, with shared Synco time scheduler
- 15.5 Case 5: Display in Desigo, andseparate time schedulers
- 15.6 Case 6: Separate display, andseparate time schedulers
- 15.7 Case 7: Separate display, andshared Synco time scheduler
- 16 Working with different tools
163/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies KNX information 2013-06-17
13.5.2 S-mode output communication objects
Flags:
R Read
T Transmit
W Write
U Update
C Communication
1)
C.S. = Company specific For internal use only
Name
Flags:
Data point type (KONNEX)
Send
See
R
W
C
T
U
heartbeat
page
Alarm info
1
0
1
1
0
219.001
DPT_AlarmInfo
yes
151
Analog input B1 / B2
1
0
1
1
0
9.001
DPT_Value_Temp
yes
155
Common alarm.
1 0 1 1 0 1.005 DPT_Alarm yes 151
Cooling coil output
1 0 1 1 0 5.001 DPT_Scaling yes 91, 95
Digital input 1
1 0 1 1 0 1.001 DPT_Switch no 154
Digital input 2
1 0 1 1 0 1.001 DPT_Switch no 154
Effective application mode
1 0 1 1 0 20.105 DPT_HVACContrMode yes 144
Effective occupancy
1 0 1 1 0 20.003 DPT_OccMode yes 40, 50
Effective room operating mode
1 0 1 1 0 20.102 DPT_HVACMode yes 42, 53
Effective room operating mode
Comfort
1 0 1 1 0 1.001 DPT_Switch yes 42, 53
Effective room operating mode
Economy
1 0 1 1 0 1.001 DPT_Switch yes 42, 53
Effective room operating mode
Precomfort
1 0 1 1 0 1.001 DPT_Switch yes 42, 53
Effective room operating mode
Protection
1 0 1 1 0 1.001 DPT_Switch yes 42, 53
Effective room temperature
1 0 1 1 0 9.001 DPT_Value_Temp yes 78
Effective setpoint
1 0 1 1 0 9.001 DPT_Value_Temp yes 69
Effective setpoint cooling
1 0 1 1 0 9.001 DPT_Value_Temp yes 69
Effective setpoint heating
1 0 1 1 0 9.001 DPT_Value_Temp yes 69
Effective setpoint offset
1 0 1 1 0 9.002 DPT_Value_Tempd yes 74
Electrical power 1 0 1 1 0 9.024 DPT_Power yes 102
Energy demand room
1 0 1 1 0 6.001 DPT_Percent_V8 yes 144
Fan output
1 0 1 1 0 5.001 DPT_Scaling yes 120
Heating coil output
1 0 1 1 0 5.001 DPT_Scaling yes 91, 95
Heating/cooling output 1 0 1 1 0 1.100 DPT_Heat/Cool yes 84
Heating outp bus el heating
1 0 1 1 0 5.001 DPT_Scaling yes 99
Heating surface output
1 0 1 1 0 5.001 DPT_Scaling yes 108
Master/slave HVAC controller
output
1 0 1 1 0 C.S.
1)
13 Byte yes 134
Master/Slave room unit output
1
0
1
1
0
C.S.
1)
4 Byte
yes
134
Outside air damper.
1 0 1 1 0 5.001 DPT_Scaling yes 114
Presence detector output
1 0 1 1 0 1.018 DPT_Occupancy yes 39
Present setpoint.
1 0 1 1 0 9.001 DPT_Value_Temp yes 69
Present setpoint...
(6 indiv. values)
1 0 1 1 0 9.001 DPT_Value_Temp yes
Present setpoints cooling
1 0 1 1 0 222.100 DPT_TempRoomSetpSetF16[3] yes 69
Present setpoints heating
1 0 1 1 0 222.100 DPT_TempRoomSetpSetF16[3] yes 69
Return air temperature output
1 0 1 1 0 9.001 DPT_Value_Temp yes 78
Room temperature output
1 0 1 1 0 9.001 DPT_Value_Temp yes 78
Status
1 0 1 1 0 C.S.
1)
2 Byte no 160
Supply air temperature output
1 0 1 1 0 9.001 DPT_Value_Temp yes 117
Window switch output
1 0 1 1 0 1.019 DPT_Window_Door yes 36, 48