Operating Instructions

Table Of Contents
162/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies KNX information 2013-06-17
13.5 S-mode communication objects for FNC
13.5.1 S-mode input communication objects
Flags:
R Read
T Transmit
W Write
U Update
C Communication
)
C.S. = Company-specific
For internal use only
Name
Flags:
Data point type (KONNEX)
Receive
See
R
W
C
T
U
timeout
page
Application mode
0
1
1
0
0
20.105
DPT_HVACContrMode
yes
145
Comfort cooling setpoint
0
1
1
0
0
9.001
DPT_Value_Temp
No
71
Comfort heating setpoint
0
1
1
0
0
9.001
DPT_Value_Temp
No
71
Cooling valve override
0
1
1
0
0
8.010
DPT_Percent_V16
No
93
Damper override
0
1
1
0
0
8.010
DPT_Percent_V16
No
96, 114
Economy cooling setpoint
0
1
1
0
0
9.001
DPT_Value_Temp
No
71
Economy heating setpoint
0
1
1
0
0
9.001
DPT_Value_Temp
No
71
Enable alarm info
0
1
1
0
0
1.003
DPT_Enable
Yes
151
Enable electric heating
0 1 1 0 0 1.003 DPT_Enable Yes 99
Enable fan command value
0
1
1
0
0
1.003
DPT_Enable
No
119
Fan command value
0
1
1
0
0
5.001
DPT_Scaling
No
119
H/C changeover input
0
1
1
0
0
1.100
DPT_Heat/Cool
Yes
84
Heating surface valve override
0
1
1
0
0
8.010
DPT_Percent_V16
No
109
Heating valve override
0
1
1
0
0
8.010
DPT_Percent_V16
No
93
Master/slave HVAC controller
input
0 1 1 0 0 C.S.
1)
13 Byte Yes 134
Master/Slave room unit input
0
1
1
0
0
C.S.
1)
4 Byte
Yes
134
Outside air temperature.
0
1
1
1
1
9.001
DPT_Value_Temp
Yes
79
Precomfort cooling setpoint
0 1 1 0 0 9.001 DPT_Value_Temp No 71
Precomfort heating setpoint
0
1
1
0
0
9.001
DPT_Value_Temp
No
71
Presence detector input
0
1
1
0
0
1.018
DPT_Occupancy
No
39
Release dampers
0
1
1
0
0
1.003
DPT_Enable
Yes
113
Relay Q24 / Q34
0
1
1
0
0
1.001
DPT_Switch
No
154
Return air temperature input
0
1
1
1
1
9.001
DPT_Value_Temp
Yes
78
Room temperature input
0
1
1
1
1
9.001
DPT_Value_Temp
Yes
78
Schedule occupancy
0
1
1
0
0
20.003
DPT_OccMode
Yes
38
Schedule room operating
mode
0 1 1 0 0 20.102 DPT_HVACMode Yes 48
Schedule usage
0 1 1 0 0 20.002 DPT_BuildingMode Yes 37
Setpoint offset
0
1
1
0
0
9.002
DPT_Value_Tempd
No
73
Setpoint...(6 indiv. values)
0
1
1
0
0
9.001
DPT_Value_Temp
No
71
Setpoints cooling
0
1
1
0
0
222.100
DPT_TempRoomSetpSetF16[3]
No
71
Setpoints heating
0
1
1
0
0
222.100
DPT_TempRoomSetpSetF16[3]
No
71
Setpoint shift cooling
0
1
1
0
0
222.101
DPT_TempRoomSetpSetShiftF16[3]
Yes
73
Setpoint shift heating
0
1
1
0
0
222.101
DPT_TempRoomSetpSetShiftF16[3]
Yes
73
Status request
0
1
1
0
0
C.S.
1)
1 Byte
No
160
Supply air temperature input
0
1
1
1
1
9.001
DPT_Value_Temp
Yes
117
Temporary Comfort mode
0
1
1
0
0
1.017
DPT_Trigger
No
41
Triac Y1 / Y2 / Y3 / Y3
0
1
1
0
0
1.001
DPT_Switch
No
154
Window switch input
0
1
1
0
0
1.019
DPT_Window_Door
No
35