Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- RXB Description of functions for FC10, FC11, FC12, FC13
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communication mode
- 4 Applications, parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode in Desigo (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use time schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode viathe Room operating mode time schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 Desigo examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via the window contact input
- 5.4.2 Central control of room operating mode via the Room operating mode time schedule
- 5.4.3 Central control of room operating mode via the Use and Occupancy time schedules
- 5.4.4 Central and local control of room operating modebased on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via the window contact input
- 5.5.2 Central control of the room operating mode via Enable Comfort
- 5.5.3 Central control of room operating mode via Room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE-Mode Examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Fan control
- 10 Master/slave
- 11 General and central functions
- 11.1 Send heartbeat and receive timeouts
- 11.2 Digital inputs
- 11.3 Temporary Comfort mode
- 11.4 Presence detector switch-on and switchoff delay
- 11.5 Heating and cooling demand
- 11.6 Heating/cooling signal output
- 11.7 Special functions
- 11.8 Boost heating (Morning Warmup, 2)
- 11.9 Night purge (Night Purge, 4), (FNC10, FNC12)
- 11.10 Precooling (Precool, 5)
- 11.11 Test mode (Test, 7)
- 11.12 Emergency heating (Emergency Heat, 8)
- 11.13 Rapid ventilation (Fan only, 9)
- 11.14 Free cooling (Freecool, 10)
- 11.15 Alarm
- 11.16 Reset the setpoint shift
- 11.17 Free inputs/outputs
- 11.18 Software version
- 11.19 Device state
- 12 Room unit
- 13 KNX information
- 14 FAQs
- 15 Integrate RXB in Desigo/Synco
- 15.1 Case 1: Integration into Synco
- 15.2 Case 2: Integration into Desigo
- 15.3 Case 3: Display in Desigo, with shared Synco time scheduler
- 15.4 Case 4: Display in Desigo/Synco, with shared Synco time scheduler
- 15.5 Case 5: Display in Desigo, andseparate time schedulers
- 15.6 Case 6: Separate display, andseparate time schedulers
- 15.7 Case 7: Separate display, andshared Synco time scheduler
- 16 Working with different tools
162/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies KNX information 2013-06-17
13.5 S-mode communication objects for FNC
13.5.1 S-mode input communication objects
Flags:
R Read
T Transmit
W Write
U Update
C Communication
)
C.S. = Company-specific
For internal use only
Name
Flags:
Data point type (KONNEX)
Receive
See
R
W
C
T
U
timeout
page
Application mode
0
1
1
0
0
20.105
DPT_HVACContrMode
yes
145
Comfort cooling setpoint
0
1
1
0
0
9.001
DPT_Value_Temp
No
71
Comfort heating setpoint
0
1
1
0
0
9.001
DPT_Value_Temp
No
71
Cooling valve override
0
1
1
0
0
8.010
DPT_Percent_V16
No
93
Damper override
0
1
1
0
0
8.010
DPT_Percent_V16
No
96, 114
Economy cooling setpoint
0
1
1
0
0
9.001
DPT_Value_Temp
No
71
Economy heating setpoint
0
1
1
0
0
9.001
DPT_Value_Temp
No
71
Enable alarm info
0
1
1
0
0
1.003
DPT_Enable
Yes
151
Enable electric heating
0 1 1 0 0 1.003 DPT_Enable Yes 99
Enable fan command value
0
1
1
0
0
1.003
DPT_Enable
No
119
Fan command value
0
1
1
0
0
5.001
DPT_Scaling
No
119
H/C changeover input
0
1
1
0
0
1.100
DPT_Heat/Cool
Yes
84
Heating surface valve override
0
1
1
0
0
8.010
DPT_Percent_V16
No
109
Heating valve override
0
1
1
0
0
8.010
DPT_Percent_V16
No
93
Master/slave HVAC controller
input
0 1 1 0 0 C.S.
1)
13 Byte Yes 134
Master/Slave room unit input
0
1
1
0
0
C.S.
1)
4 Byte
Yes
134
Outside air temperature.
0
1
1
1
1
9.001
DPT_Value_Temp
Yes
79
Precomfort cooling setpoint
0 1 1 0 0 9.001 DPT_Value_Temp No 71
Precomfort heating setpoint
0
1
1
0
0
9.001
DPT_Value_Temp
No
71
Presence detector input
0
1
1
0
0
1.018
DPT_Occupancy
No
39
Release dampers
0
1
1
0
0
1.003
DPT_Enable
Yes
113
Relay Q24 / Q34
0
1
1
0
0
1.001
DPT_Switch
No
154
Return air temperature input
0
1
1
1
1
9.001
DPT_Value_Temp
Yes
78
Room temperature input
0
1
1
1
1
9.001
DPT_Value_Temp
Yes
78
Schedule occupancy
0
1
1
0
0
20.003
DPT_OccMode
Yes
38
Schedule room operating
mode
0 1 1 0 0 20.102 DPT_HVACMode Yes 48
Schedule usage
0 1 1 0 0 20.002 DPT_BuildingMode Yes 37
Setpoint offset
0
1
1
0
0
9.002
DPT_Value_Tempd
No
73
Setpoint...(6 indiv. values)
0
1
1
0
0
9.001
DPT_Value_Temp
No
71
Setpoints cooling
0
1
1
0
0
222.100
DPT_TempRoomSetpSetF16[3]
No
71
Setpoints heating
0
1
1
0
0
222.100
DPT_TempRoomSetpSetF16[3]
No
71
Setpoint shift cooling
0
1
1
0
0
222.101
DPT_TempRoomSetpSetShiftF16[3]
Yes
73
Setpoint shift heating
0
1
1
0
0
222.101
DPT_TempRoomSetpSetShiftF16[3]
Yes
73
Status request
0
1
1
0
0
C.S.
1)
1 Byte
No
160
Supply air temperature input
0
1
1
1
1
9.001
DPT_Value_Temp
Yes
117
Temporary Comfort mode
0
1
1
0
0
1.017
DPT_Trigger
No
41
Triac Y1 / Y2 / Y3 / Y3
0
1
1
0
0
1.001
DPT_Switch
No
154
Window switch input
0
1
1
0
0
1.019
DPT_Window_Door
No
35