Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Room unit 2013-06-17
In room units with an LCD, it is possible to define what is to be displayed in the event of
a setpoint shift.
Parameter
LCD display
HandyTool
Setpoint display
(only room units with LCD).
*110
Relative
Shift value e.g. +3.0K (basic setting)
0
Absolute Effective temperature setpoint, e.g. 23.0 °C
(Mean value between heating and cooling setpoint).
4
If "Absolute setpoint adjustment" is selected, the LCD panel displays a scale which
illustrates the adjustment as it happens:
10385Z20
To reset the setpoint shift, refer to page 152.
This parameter controls the reaction of the application, when the standby button " " on
the room unit is pressed.
Parameter
Description
HandyTool
Fan function standby
*168
OFF (basic setting)
Room operating mode Precomfort, Economy or
Protection (see section 5)
Automatic fan control
0
ON
Room operating mode Precomfort, Economy or
Protection
Fan disabled
1
The fan stage values on the room unit (I, II, III) are mapped to fixed or adjustable speed
values (%).
Parameter
Description
*169
Fan speed user defined
Disabled
Fixed fan speed values 0 - 50 - 100%
0
Enabled
Adjustable fan speed values (P170…P172)
1
If P169 = 1
Basic setting
Range
Resolution
HandyTool
User fan speed 3
100 %
0...100 %
1 %
*170
User fan speed 2
50 %
0...100 %
1 %
*171
User fan speed 1
0 %
0...100 %
1 %
*172
Temperature display in
case of a setpoint shift
Note
Fan function standby
(FC-13 only)
Fan speed user defined
(FC-13 only)