Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- RXB Description of functions for FC10, FC11, FC12, FC13
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communication mode
- 4 Applications, parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode in Desigo (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use time schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode viathe Room operating mode time schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 Desigo examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via the window contact input
- 5.4.2 Central control of room operating mode via the Room operating mode time schedule
- 5.4.3 Central control of room operating mode via the Use and Occupancy time schedules
- 5.4.4 Central and local control of room operating modebased on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via the window contact input
- 5.5.2 Central control of the room operating mode via Enable Comfort
- 5.5.3 Central control of room operating mode via Room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE-Mode Examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Fan control
- 10 Master/slave
- 11 General and central functions
- 11.1 Send heartbeat and receive timeouts
- 11.2 Digital inputs
- 11.3 Temporary Comfort mode
- 11.4 Presence detector switch-on and switchoff delay
- 11.5 Heating and cooling demand
- 11.6 Heating/cooling signal output
- 11.7 Special functions
- 11.8 Boost heating (Morning Warmup, 2)
- 11.9 Night purge (Night Purge, 4), (FNC10, FNC12)
- 11.10 Precooling (Precool, 5)
- 11.11 Test mode (Test, 7)
- 11.12 Emergency heating (Emergency Heat, 8)
- 11.13 Rapid ventilation (Fan only, 9)
- 11.14 Free cooling (Freecool, 10)
- 11.15 Alarm
- 11.16 Reset the setpoint shift
- 11.17 Free inputs/outputs
- 11.18 Software version
- 11.19 Device state
- 12 Room unit
- 13 KNX information
- 14 FAQs
- 15 Integrate RXB in Desigo/Synco
- 15.1 Case 1: Integration into Synco
- 15.2 Case 2: Integration into Desigo
- 15.3 Case 3: Display in Desigo, with shared Synco time scheduler
- 15.4 Case 4: Display in Desigo/Synco, with shared Synco time scheduler
- 15.5 Case 5: Display in Desigo, andseparate time schedulers
- 15.6 Case 6: Separate display, andseparate time schedulers
- 15.7 Case 7: Separate display, andshared Synco time scheduler
- 16 Working with different tools
158/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Room unit 2013-06-17
The display of the heating and cooling symbols can be enabled or disabled. Note that
this applies only to room units with an LCD display.
Symbols:
Cooling sequence active
Heating sequence active
Parameter
Description
Basic setting
Heating/cooling symbol display
Heating and cooling symbols are displayed
Enabled
The room temperature can be displayed either in Celsius (°C) or Fahrenheit (°F). Note
that this applies only to room units with an LCD display.
Parameter
Value
HandyTool
Temperature unit
(only room units with LCD)
*108
Celsius (°C) (basic setting)
1
Fahrenheit (°F)
0
In room units with an LCD panel, it is also possible to select the temperature value
to be displayed.
(Normal mode = setpoint not shifted or setpoint shift canceled).
Parameter
LCD display
HandyTool
Standard display Basic setting: Room temperature
(only room units with LCD).
*109
No display
Setpoint + scale
setpoint shift *)
Setpoint
Room temperature +
scale setpoint shift *)
Room temperature
Displays only the room operating mode and, if activated,
the heating or cooling symbol.
Effective temperature setpoint (average value from
heating and cooling setpoints) e.g. SpH = 21 °C and
SpC = 24 °C) and scale with setpoint adjustment.
Effective temperature setpoint (average value from
heating and cooling setpoints) e.g. SpH = 21 °C and
SpC = 24 °C.
Effective room temperature used as the input to the
controller (basic setting) and scale with setpoint
adjustment.
Effective room temperature used as the input to the
controller (basic setting)
96
56
48
10
2
*)RXB39.1 only
Displaying heating and
cooling symbols
(ETS only)
Selecting the
temperature unit
Temperature display in
normal mode