Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Room unit 2013-06-17
Parameters (Description see below)
Basic setting
HandyTool
Measured value correction
0.0 K
*101
Setpoint adjustment range
± 3 K
*103
Local Comfort mode
Enabled
*105
Room unit (Handy tool: fixed as "With LCD")
Without LCD
--
Temperature unit (only room units with LCD)
Degrees Celsius
*108
Standard display (only room units with LCD)
Room temperature
*109
Setpoint display (only room units with LCD)
Relative
*110
Fan function standby
Disabled (0)
*168
Fan speed user defined
Disabled (0)
*169
User fan speed 3
100 %
*170
User fan speed 2
50 %
*171
User fan speed 1
0 %
*172
Parameters for fan control
Description see section 9.2 (1...3 stage fan), section 9.3.3 (DC 0...10 V fan)
The measured value of the built-in temperature sensor can be recalibrated to
compensate for radiation from a cold wall, for example.
Parameter
Basic setting
Range
Resolution
HandyTool
Measured value correction
0 K
– 3...3 K
0,1 K
*101
This correction is also valid for a sensor that is connected to the analog input B1 (but
not for a bus sensor).
The maximum setpoint adjustment range is as follows (see also page 73).
Parameter
Basic setting
Range
Resolution
HandyTool
Setpoint adjustment range
± 3 K
± 0...10 K
1 K
*103
A management station can use the communication object Enable Comfort (see
page 58) to prevent the room operating mode from being higher than Economy (energy
conservation). Local comfort mode can be ignored by setting the following parameter:
Parameter
Description
HandyTool
Local Comfort mode
switch from Economy to Comfort or Precomfort mode
*105
Enabled (basic setting).
This means that Comfort or Precomfort may be
disabled by the input Local comfort mode.
1
Disabled (Ignore Local comfort mode).
Comfort or Precomfort may NOT be disabled by the
input Local comfort mode.
2
You can choose if the room unit is equipped with an LCD display. If so, the parameters
hereafter can also be set. The HandyTool has a fixed setting "With LCD".
Parameter
Description
Basic setting
Room unit
Without LCD / With LCD
Without LCD
Sensor correction
Note
Setpoint adjustment
range
Local comfort mode
(in LTE mode only)
Room unit