Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- RXB Description of functions for FC10, FC11, FC12, FC13
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communication mode
- 4 Applications, parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode in Desigo (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use time schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode viathe Room operating mode time schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 Desigo examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via the window contact input
- 5.4.2 Central control of room operating mode via the Room operating mode time schedule
- 5.4.3 Central control of room operating mode via the Use and Occupancy time schedules
- 5.4.4 Central and local control of room operating modebased on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via the window contact input
- 5.5.2 Central control of the room operating mode via Enable Comfort
- 5.5.3 Central control of room operating mode via Room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE-Mode Examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Fan control
- 10 Master/slave
- 11 General and central functions
- 11.1 Send heartbeat and receive timeouts
- 11.2 Digital inputs
- 11.3 Temporary Comfort mode
- 11.4 Presence detector switch-on and switchoff delay
- 11.5 Heating and cooling demand
- 11.6 Heating/cooling signal output
- 11.7 Special functions
- 11.8 Boost heating (Morning Warmup, 2)
- 11.9 Night purge (Night Purge, 4), (FNC10, FNC12)
- 11.10 Precooling (Precool, 5)
- 11.11 Test mode (Test, 7)
- 11.12 Emergency heating (Emergency Heat, 8)
- 11.13 Rapid ventilation (Fan only, 9)
- 11.14 Free cooling (Freecool, 10)
- 11.15 Alarm
- 11.16 Reset the setpoint shift
- 11.17 Free inputs/outputs
- 11.18 Software version
- 11.19 Device state
- 12 Room unit
- 13 KNX information
- 14 FAQs
- 15 Integrate RXB in Desigo/Synco
- 15.1 Case 1: Integration into Synco
- 15.2 Case 2: Integration into Desigo
- 15.3 Case 3: Display in Desigo, with shared Synco time scheduler
- 15.4 Case 4: Display in Desigo/Synco, with shared Synco time scheduler
- 15.5 Case 5: Display in Desigo, andseparate time schedulers
- 15.6 Case 6: Separate display, andseparate time schedulers
- 15.7 Case 7: Separate display, andshared Synco time scheduler
- 16 Working with different tools
153/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies General and central functions 2013-06-17
11.17 Free inputs/outputs
In a building automation and control system, the free I/Os can be used to interrogate
switch states, for example, or for direct switch control of another device over the network.
However, these functions are not suitable for time-critical processes (<1 s).
Free inputs can be defined as "open" or "closed" (see 11.2).
If not already in use, the following inputs and outputs can be used freely:
RXB21.1/FC-10
Appli-
cation
Digital inputs
Outputs (Triac)
Outputs
(relay)
D1
D2
Y1
Y2
Y3
Y4
Q24
Q34
FNC02
♦
♦
•
•
•
FNC04
♦
♦
•
•
FNC08
♦
♦
FNC20
♦
♦
X X
•
•
RXB21.1/FC-11 Appli-
cation
Digital inputs
Outputs (Triac)
Outputs
(relay)
D1
D2
Y1
Y2
Y3
Y4
Q24
Q34
FNC10
♦
♦
•
X X
FNC12
♦
♦
X X
FNC18
♦
♦
∅
1)
∅
1) 2) 2)
1) Heating surface valve
2) Fan-coil valve
RXB22.1/FC-12 Appli-
cation
Digital inputs
Outputs (Triac)
Outputs (Relay)
D1
D2
Y1
Y2
Q24
Q34
Q44
FNC03
♦
♦
•
X
FNC05
♦
♦
X
RXB39.1/FC-13
Appli-
cation
Digital inputs DC 0…10 V
outputs
Outputs
(Relay)
D1
D2
D3
D4
YC1
YC2
YC3
Q14
Q34
FNC02
♦
♦
♦
♦
X
X
X
X
X
FNC03
♦
♦
♦
♦
X X X X X
FNC04
♦
♦
♦
♦
X X X X X
FNC08
♦
♦
♦
♦
X X X X X
Digital inputs
♦
If "Not used" (see page 142), may be used freely for other
purposes.
Triac outputs,
X Used by the application
• May be used freely for other purposes
•
Only freely usable with bus valve actuators
Only freely usable with bus valve actuators
All combinations: see CM110672)
∅ Not freely usable
Relay outputs
X Used by the application
May be used freely in applications with single-speed or
2-speed fan, (see page 122).
The setting of parameters for unused inputs is described in Section 11.2, page 142.
Key