Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies General and central functions 2013-06-17
EnableAlarmInfo (Input)
Possible partner function blocks
Known partner devices
EnableAlarmInfo
Siemens
Synco RMU710 / 20 / 30,
RMH760, RMB795, RMS705
Broadcast
Error code Short name
4910 RXB room temp. sensor error
4920 RXB room temperature frost
4925 RXB supply air temp sensor error
4940 RXB outside temperature frost
4950 RXB el air heater overtemp
4960 RXB general fault
4970 RXB PPS fault
4980 RXB no airflow
For more information on the alarm concept, see "Communication on the bus, Synco700
& RXB", CE1P3127.
11.16 Reset the setpoint shift
When the system changes from Comfort or Precomfort to Economy or Protection mode
(see page 73), the setpoint shift can be canceled. This function can be enabled and
disabled via Central functions.
The setpoint adjustment can only be cancelled with the QAX34.1 and QAX84.1 room
units, which have an LCD display. Enabling this function in room units with a
mechanical setpoint adjuster (potentiometer) will cause errors in data transmission.
HandyTool
Parameter Description Range Basic setting
*137 Reset setpoint offset 0 = Disabled
1 = Enabled
Disabled
Display on a Synco
device:
STOP
Note!