Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies General and central functions 2013-06-17
ETS Professional
Go to the Functions menu for the disable feature.
HandyTool See parameters in the last column of the above table.
The special functions are disabled if the user requires manual (P093) or reduced
(P168) operation on the room unit.
11.8 Boost heating (Morning Warmup, 2)
This function is used to raise the temperature in a room as quickly as possible to the
Precomfort heating setpoint at the end of the night setback period.
Objective: Preheat the room for heating.
100
0
TR
Y [%]
10385D23en
SpH
Pcf
SpC
Pcf
Fan
Heating coil
The following conditions must be fulfilled:
The room controller must be in Economy mode.
The function can be disabled in the room controller by means of P134 or the ETS tool.
The function must be enabled via the building automation and control system
(communication object Application mode, see page 145).
The function is disabled via the building automation and control system.
11.9 Night purge (Night Purge, 4), (FNC10, FNC12)
This function is used to cool rooms to the Comfort cooling setpoint, in readiness for
normal occupancy, using the outside air damper. Here, only the fan is active, not the
cooling coil.
Objective: Save energy by using "free of charge", cold outside air.
100
TR
0
Y [%]
SpH
Cmf
SpC
Cmf
10285D24
Ventilator
STOP
Note!
Enabling the function
Initiating the function
Terminating the function