Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies General and central functions 2013-06-17
11.7 Special functions
The special functions described in sections 11.8 ff are triggered by the following S-
mode communication object:
Application mode (Input communication object)
Flags
Type Receive
timeout
States
R
W
C
T
U
0 1 1 0 0 20.105
DPT_HVAC
ContrMode
yes
0 = Auto
1 = Heat
2 = Morning Warmup
3 = Cool
4 = Night Purge
5 = Precool
6 = Off
7 = Test
*)
8 = Emergency Heat
9 = Fan Only
10 = Freecool
Other states not used
*) Exit from Test mode (7) is only possible with sequence Off (6) + normal mode (0).
The following communication object is used in LTE mode:
Application mode (Input)
Possible partner function blocks
Known partner devices
ContrMode
104 PMC
Programs to HVAC-Mode Conversion
109 BOS
Building/Occ-Mode Source
115 HVACOPT
HVAC Optimizer
Siemens:
Synco RMB795
Timeswitch
zone
State Description See
section
Para-
meter
0 = Auto
Controller operating normally.
1 = Heat
Controller can operate in heating mode only;
cooling sequence disabled.
--
2 = Morning Warmup
Boost heating.
11.8
*134
3 = Cool
Controller can operate in cooling mode only;
heating sequence disabled.
--
4 = Night Purge
Night purge:
Precool room with fan (no cooling coil) (only
FNC10, FNC12 with outside air damper)
11.9
*138
5 = Precool
Precool:
Precool the room with fan, cooling coil and
outside air damper.
11.10
*135
6 = Off The temperature control is disabled.
The remaining functions are active.
Communications are operating as normal.
--
7 = Test *)
All functions disabled.
Motorized valve and damper actuators
synchronized.
Outputs can be overridden via KNX bus.
11.11
8 = Emergency Heat
Emergency heating (always enabled).
11.12
9 = Fan only
Rapid ventilation (formerly Air flush)
Max. ventilation using outside air (FNC10,
FNC12 with outside air damper only).
11.13
*136
10 = Freecool Free cooling:
During Economy. Precool room using cooling
coil (low energy tariffs).
During Comfort normal mode.
11.14
*135
*) Exit from Test mode (7) is only possible with sequence Off (6) + normal mode (0).
Triggering the special functions by the building automation and control system can be
disabled in each room controller via tool.