Operating Instructions

Table Of Contents
142/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies General and central functions 2013-06-17
11.2 Digital inputs
The following volt-free contacts can be connected to digital inputs D1 and D2:
Presence detector or window contact (for details of this function see Section 5).
Safety thermostat electric heating coil / reheater (for details of this function, see
page 96).
Safety thermostat outdoor temperature (for details of this function, see page 109).
Digital input
Function
Type of operation
HandyTool
See section
Input 1
Input 2
Input 3
Input 4
*113
*114
*115
*116
Not used by the
application
Free: Bus = 1 = Contact closed
Free: Bus = 1 = Contact open
0= Default
1
(Contact may be used freely (see page 153 )
Occupancy Occupied = Contact closed
Occupied = Contact open
2
3
Window Window open = Contact open
Window open = Contact closed
4
5
5
Safety thermostat
el. heating coil
Overtemp = Contact open
Overtemp = Contact closed
16
17
8.3
Safety thermostat
Outside temperature
OT < frost = Contact closed
OT < frost = Contact open
(applications with outside air damper only)
32
33
8.5
No air flow
No flow = Contact closed
No flow = Contact open
34
35
see below
Do not connect the same type of sensor/functions to more than one digital input.
The controller would ignore the second input.
t
Fan start No air circulation detected
30 s (debouncing)
Alarm is possible Alarm is issued
30 s (fan start phase)
t
Fan start No air circulation detected
30 s (fan start phase)
Alarm is possible
30 s (debouncing)
Alarm is issued
El. heater disabled El. heater enabled
Fan overrun time
El. heater disabled
Fan off
The figures above illustrate the air circulation alarm function of the room controller:
An alarm is only possible 30 s after the controller has given a fan command (fan start
phase).
A closed alarm contact is ignored for 30 s (debouncing), only then an alarm message
is issued.
An electric heater is disabled during the fan start phase (30 s).
When an alarm message is issued, the electric heater is disabled immediately;
the fan will continue to run during the fan overrun time defined by P098.
Note
"No airflow"
Function with el. heater