Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Master/slave 2013-06-17
10.3 LTE mode with zones
The master/slave configuration is also possible in LTE mode. However, you do not
need to create the individual bindings, but instead define the master/slave zone.
Here too, the following applies: The slaves must be controlled by only one master, and
master/slave bindings are only possible between controllers with the same version
(ASN) featuring the same applications and settings.
Select Master / Slave:
M
S
S
Room
321
322
323
Geogr. zone
5.1.1
5.2.1
5.3.1
Master / Slave
Master
Slave
Slave
M/S zone
5.1.1
5.1.1
5.1.1
Geogr. zone und M/S zones need not be the same. However, every day work is easier
because you see directly to which master a slave belongs.
Select Master/Slave:
The master/slave function requires that all 3 M/S zones have the same name
If the master/slave function is not required, the M/S zone should be disabled (to limit
the load on the bus).