2.2 Supported tools
The RXB Konnex controllers can be commissioned with the following tools:
ETS Professional (ETS3 and later supports RXB2... ; ETS4 and later supports RXB39.1)
Synco ACS (V 5.10 and later supports RXB2... ; V8.22 and later supports RXB39.1).
HandyTool l (QAX34.3).
Be careful when using different tools. The following rule applies:
Last one's right!
If you use OCI700 as an interface, it is connected to the service plug of the controller
or of the room unit.
As long as the OCI700 is connected to the service plug, it must be supplied by
the computer via the USB interface. Otherwise the LCD display of the room unit
will turn dark and the controller will switch to addressing mode.
2.3 Parameter setting with ETS Professional
This manual does not describe how the physical address is defined.
Refer to the EIB manual for more details.
Open the project and select a device.
To start the parameter setting, select the Parameters tab.
STOP
Note!
ETS Professional