Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Fan control 2013-06-17
The following settings can be selected:
Parameter
Description
HandyTool
Fan speeds
(RXB2... only)
*094
External
fan control
No influence on fans by controller or room unit.
The fan is e.g. operated manually at the fan coil.
The controller switches on relay Q14 in operating state Comfort, thus
allowing for enabling fan operation.
Note: For other operating states but Comfort, the fan is enabled by
the fan algorithm.
Warning! With FNC03 (electric re-heater) the fan must not be
switched off while the re-heater is active, and a fan overrun must be
assured, in order to avoid overheating.
0
1-speed
Single-speed fan control with relay Q14.
1
2-speed
Two-speed fan control with relays Q14 and Q24.
2
3-speed
Three-speed fan control with relays Q14, Q24 and Q34.
3
Fan control
*093
Auto Fan speeds are changed over automatically (by the room controller).
Manual fan speed presetting is possible only in operating mode
Comfort.
1
Manual All fan stages can only be set manually (on the room unit via PPS2).
Exception: The fan changes to automatic operation when the room
temperature is outside the Protection setpoints.
0
The motors of some fans do not have a sufficiently powerful torque to set the fan in
motion at the lowest speed. Multi-speed fans are, therefore, always started at the
highest speed and then switched back to fan speed 1.
This feature also applies to manual fan-speed control via the room unit.
The unused relay outputs are freely available for other purposes (see page 153)
Fan startup behavior
Notes