Operating Instructions

Table Of Contents
121/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Fan control 2013-06-17
9.2 Fan parameter setting 1 / 2 / 3-step
Select Fan control, Fan speeds.
Select Fan control:
HandyTool See Parameters in the last column of the table below
Paramete
Basic setting
Range
Resolution
HandyTool
Fan speed
3-speed
(see below)
*094
Fan control
Auto
Manual, Auto
*093
Temperature sensor B1
See 7.1.2
Minimum on time
6 min
1...10 min
1 min
*095
Fan overrun time
1 min
1...10 min
1 min
*098
Periodic fan kick Comfort
OFF
0...89 min ; Off
1 min
*096 1)
Periodic fan kick Economy
OFF
0...359 min ; Off
1 min
*097 1)
1) HandyTool: 90 min / 360 min = OFF
ETS Professional
ACS
9.5
7.1.2
9.7
9.6
9.5
7.1.2
9.7
9.6