Operating Instructions

Table Of Contents
116/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Control sequences 2013-06-17
8.6.1 Parameterizing
Basic functions: see sections 8.1.1 through 8.1.7.
Minimum supply air temperature and Maximum supply air temperature must be
parameterized during engineering.
Select Other setpoints:
Select Other setpoints.
HandyTool See Parameters in the last column of the table below
Parameter
Basic
setting
Range Resolution HandyTool
parameter
Minimum supply air
temperature
16 °C
10 °C to Comfort heating setpoint
0.5 °C *038
Maximum supply air
temperature
35 °C
Comfort cooling setpoint to 40 °C
RXB39.1: ...to 50°C
0.5 °C *039
ETS Professional
ACS