Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Control sequences 2013-06-17
Select Sequences, Other setpoints:
HandyTool See Parameters in the last column of the table below
Parameter outside air supply
Basic
setting
Range
Resolution
HandyTool
parameter
Outdoor temp. min. damper pos.
16°C
10 °C...40°C *)
0,5°C
*073
Outside air damper runtime
150s
0...360s
1s
*074
Min. damper position
0%
0...100%
1%
*075
*) By temporarily adjusting the setpoint if necessary, the application ensures that
there is a differential of at least 1K between the Outside air temp. min. damper
pos. setpoint and the cooling setpoint of the effective room operating mode.
8.5.2 Enabling of the function
The function can be centrally disabled or enabled.
Basic setting: the outside air damper is enabled.
The following S-mode communication object is used to integrate the damper enabling:
Enable dampers (Input communication object)
Flags
Type Receive timeout States
R
W
K
T
U
0 1 1 0 0 1.003
DPT_Enable
yes 0 = Disable = damper closed
1 = Enable = automatic control
The following communication object is used in LTE-mode:
Enable dampers (Input)
Possible partner function blocks Known partner devices
DisableDamper
115 HVACOpt
HVAC-Optimizer
Siemens:
---