Operating Instructions

Table Of Contents
111/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Control sequences 2013-06-17
HandyTool See Parameters in the last column of the table below
Parameter for downdraft
compensation
Basic
setting
Range
Resolution
HandyTool
parameter
Outdoor temp.0% valve position
0 °C
30...10 °C
0.5 K
*078
Outdoor temp. max. valve
position
10 °C 30...10 °C 0.5 K *079
Max. valve position
100 %
0...100 %
1 %
*080
The following conditions must be fulfilled:
The room controller must be in Comfort mode
The radiator must not be disabled (e.g. by application mode = COOL).
8.5 Outside air damper fan coils
("Economizer", FNC10, FNC12)
The outside air damper mainly serves to provide the room with fresh outside air. In
addition, the outside air can be used to cool the room.
The outside air damper is always operated in Comfort and Precomfort modes.
In Economy mode, it is operated only in conjunction with the following special functions
(see page 145 ff. for a description):
Pre-Cool, Free Cool, Night Purge and Fan-Only.
The damper is controlled through a stroke model calculated from the runtime of the
actuator.
The Economizer setpoint Outside air temp. min. damper pos. defines at which outside
temperature the outside air damper is opened to an adjustable minimum position.
This minimum position ensures a constant air supply below the outside air temperature.
The Outside air temp. min. damper pos. setpoint should be selected to ensure that
there is at least a difference of 4 K between this value and the cooling setpoint and that,
at the same time, no draught is caused by the inflow of cold outside air.
The Economizer setpoint should not be much lower than the Comfort heating setpoint,
otherwise too much cool air would come into the room during the heating sequence.
Above the Outside air temp. min. damper pos. setpoint, the damper is opened
beyond the minimum position if:
the outside temperature is below the room temperature and
either the room controller is in Comfort or Precomfort room operating mode
or
one of the special functions "Pre-Cool", "Free Cool", "Night Purge" or "Fan-Only" is
active
Enabling the function
Control sequence,
damper actuator