Operating Instructions

Table Of Contents
10/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Introduction 2013-06-17
1.8.2 LTE mode
LTE mode was specifically designed to simplify engineering. Unlike with S-mode, there
is no need to create the individual connections (group addresses) in the tool. The
devices autonomously establish connections.
In order to make this possible, the following circumstances are predefined:
Every device or sub-device is located within a zone
Every data point (input or output) is assigned to a zone
Every data point (input or output) has a precisely defined "name".
Whenever an output and an input with the same "name" are located in the same zone,
a connection is established automatically, as shown in the following diagram.
Controller
Valve
Sensor
Time switch zone 1. 1. 1
Outside temperature zone 3
Geogr. zone 2.5.1Geogr. zone 2.5.1
Heat distr zone 1
Cooling coil
Outside temperature
10385Z01en
Outside temperature
Cooling coil
Outside temperature zone 3
The following types of zone are defined:
"Geographical" zones (Syntax: Apartment . Room . Subzone).
The timeswitch zone is a "geographical" zone used for special purposes
Outside temperature zones
Heat distribution zones
For further details, refer to the Konnex specification.
Definitions
Types of zone