RXB (KNX) applications library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 (RXB applications see document CM110672 Supplementary documents CM110672 CM1Y9775 CM1Y9776 CM1Y9777 CM1Y9778 CM1Y9779 CM110385en_08 2013-06-17 RXB applications from FC-10, FC-11, FC-12, FC-13 RXB Integration – S-Mode RXB / RXL Integration – Individual Addressing 3rd Party Integration Synco Integration Working with ETS Building Technologies
Table of contents 1 Introduction ...................................................................................................6 1.1 Validity of the documentation ........................................................................6 1.2 Revision history .............................................................................................6 1.3 Copyright .......................................................................................................7 1.4 Quality assurance ....
5.4.1 5.4.2 5.4.7 5.4.8 Local control of room operating mode via the window contact input .......... 47 Central control of room operating mode via the Room operating mode time schedule...................................................................................................... 48 Central control of room operating mode via the Use and Occupancy time schedules ....................................................................................................
8.3 8.3.1 8.3.2 8.3.3 8.3.4 Fan coils with an electric reheater ...............................................................96 4-pipe fan-coils with electric reheater ..........................................................97 2-pipe fan-coils with electric reheater ..........................................................97 Electric reheater RXB21.1 (relay) ...............................................................99 Electric reheater RXB39.1 (DC 0...10 V plus relay) ............................
11.12 Emergency heating (Emergency Heat, 8) ................................................. 148 11.13 Rapid ventilation (Fan only, 9) .................................................................. 149 11.14 Free cooling (Freecool, 10) ....................................................................... 150 11.15 11.15.1 11.15.2 Alarm......................................................................................................... 150 S-mode ............................................
1 Introduction 1.1 Validity of the documentation Devices with production date up to approx. December 2007 Devices with procuction date from approx. January 2008 RXB21.1/FC-10 Index A RXB21.1/FC-11 Index A RXB22.1/FC-12 Index A QAX34.3 Series A - C RXB21.1/FC-10 Index B and higher RXB21.1/FC-11 Index B and higher RXB22.1/FC-12 Index B and higher RXB39.1/FC-13 Index A and higher QAX34.3 Series D and higher – Documentation revisions _03 and higher apply.
CM110385en_02 20.09.2006 • • • • • • • • • • CM110385en_01 31.07.2006 • First edition New Section 1.3 Moved note from 8.1.3 page 78 to 8.1.4 page 81 Bus valve output heating/cooling actuator deleted (pages 78 and134) 7.1.5 Konnex bus sensors: cyclic sending must be enabled 8.1.4 page 81: deleted "Note!" Pages 119 and 124: Rapid ventilation (Parameter 136) 11.17: tables for free inputs/outputs 13.6, 13.
1.6 Target audience, prerequisites This document assumes that users of the RXB Konnex controllers are familiar with the tools ETS Professional and/or Synco ACS and able to use them. It also presupposes that these users are aware of the specific conditions associated with EIB/KNX. In most countries, specific EIB/KNX know-how is transmitted through training centers certified by the EIBA (see www.eiba.com/ or www.konnex.org/). For details concerning the Konnex bus see document CE1N3127.
1.7 Bus supply for RXB controllers RXB controllers can work without bus supply if the following conditions are adhered to: • • • • • Parameterize only using the HandyTool (not with ETS or ACS). No integration in a building automation and control system (e.g. Desigo, Synco). No changeover mode (sensor signal via bus). No outdoor temperature via bus No master/slave combinations. Otherwise, the Konnex bus, used by the RXB room controller for communication, requires a bus supply.
1.8.2 LTE mode LTE mode was specifically designed to simplify engineering. Unlike with S-mode, there is no need to create the individual connections (group addresses) in the tool. The devices autonomously establish connections. Definitions In order to make this possible, the following circumstances are predefined: • Every device or sub-device is located within a zone • Every data point (input or output) is assigned to a zone • Every data point (input or output) has a precisely defined "name".
2 Definitions / Tools 2.1 Signals and parameters (presentation) The inputs, outputs and parameters of an application can be influenced in various ways. These are identified by the following symbols in this description of functions: Room unit Parameters identified by this symbol are influenced by the room unit. ETS Professional Parameters identified by this symbol are set using ETS Professional (EIB tool software). STOP The RXB2... KNX controller parameters can be set with ETS3 and later. The RXB39.
Note LTE-mode communication objects A list of all S mode communication objects is located in section 13.5; a detailed description of the Konnex data types in section 13.9.
2.2 Supported tools The RXB Konnex controllers can be commissioned with the following tools: • ETS Professional (ETS3 and later supports RXB2... ; ETS4 and later supports RXB39.1) • Synco ACS (V 5.10 and later supports RXB2... ; V8.22 and later supports RXB39.1). • HandyTool l (QAX34.3). STOP Note! • Be careful when using different tools. The following rule applies: Last one's right! • If you use OCI700 as an interface, it is connected to the service plug of the controller or of the room unit.
2.4 ACS Parameter setting in ACS This manual does not describe how the physical address is defined. This information can be found in the ACS description.
2.5 HandyTool Parameter setting using the HandyTool Tthe QAX34.3 room unit contains the function "HandyTool" allowing you to parameterize the RXB room controllers (from version 2.36). The following settings are possible in the room controllers: • Parameter • Physical address • Zones Group addresses (bindings) cannot be assigned. This must be carried out in ETS. QAX34.3 mmroom unit In addition to its room unit functionality, this device also allows for parameterizing the room controllers.
2.5.1 Operation of the HandyTool functions Function of the buttons + = count/move up – = count/move down (quit without acknowledgement) < = Enter (Confirm) 10385Z70 > = Escape Display • Parameter position • Value to be adjusted Restart after important parameter changes e.g. P006 e.g. 22.5 (a temperature) or 250 (e.g. a particular actuator type) After modification of certain parameters (e.g. *063 Actuator type), the controller will perform a restart. 2.5.
Adjustable parameters (Parameter mode) P001 P002 P003 P008 P009 P010 P011 P012 P013 P014 P015 P016 P018 Physical address Physical address Physical address Geographical zone (Apartment) Geographical zone (Room) Geographical zone (Subzone) Timeswitch zone (Apartment) Timeswitch zone (Room) Timeswitch zone (Subzone) Heat distr. zone heating coil Refr. distr. zone cooling coil Heat distr.
+/– allows for finding the number and pressing < (Enter) confirms it. The corresponding value is displayed. +/– allows for modifying the value and pressing < (Enter) confirms it. > (Escape) returns to list without changing anything. Pressing Escape one more time opens the list with the modes. Pressing Escape a third time returns to the normal mode (room unit). Note The parameter numbers are located in sections 13.6 and 13.7 as well as in the sections where the functions are described.
If 4 or 5 is displayed, this mode can be selected via < (Enter). The storage number (c1) is displayed and can be changed via + / – . Select the desired storage (1...5) via < (Enter). Uploading • If storage is empty, upload begins and the display flashes. OK is displayed after successful upload. • If the storage is full, "dEL" for "Delete?" is displayed. Pressing <(Enter) at this time overwrites the existing set. If you press > (Escape), the storage number which you can change via + / – is displayed.
Theoretically possible positions for periphery testing: T 01 Sensor input B1 9) Value of B1 in °C. 9) T 11 T 12 Digital input D1 Digital input D2 T 21 Heating valve 1) 2) 7) 8) T 22 Cooling valve 1) 2) 7) 8) T 23 El. Heating register T 25 Heating surface T 27 Damper T 31 Fan relay T 41 T 42 T 43 Relay Q14 Relay Q24 Relay Q34 T T T T Triac Y1 Triac Y1 Triac Y3 Triac Y4 51 52 53 54 True state of the contact at D1 (0 = open; 1 = closed).
3 Select communication mode As stated in section 1, the RXB Konnex room controllers operate either in S-mode or LTE mode. They are used in S-mode when networked with the Desigo building automation and control system, and in LTE mode with the Synco system. Note ETS Professional The factory setting of all controllers and the basic setting of the tools is 0 = S-Mode. This minimizes the bus load. Exception: ACS changes the setting immediately to 1 = LTE + S. The ETS Professional is used in Desigo networks.
3.1 Zone addressing in LTE mode (in conjunction with Synco) This section applies only to LTE mode. In cases where RXB Konnex controllers are used in LTE mode (e.g. in conjunction with Synco) zone addresses need to be allocated. These must be defined together with the Synco devices at the planning stage. The zones to be defined are as follows: Geographical zone (Apartment . Room Subzone) Apartment = ---, 1...126 Room = ---, 0...63 Subzone =---, 0...15 Timeswitch zone (Apartment .
Outside air temperature zone Zone The outside air temperature (all Synco devices of series 700) is exchanged in this zone. = ---, 1...31 Master/slave zone (Apartment . Room Subzone) Apartment = ---, 1...126 Room = ---, 0...63 Subzone =---, 0...15 In cases where RXB controllers are to be operated in master/slave mode, a master/slave zone must also be defined. For the master, it is usual to enter the "geographical" zone of the master. The same master/slave zone is used for the slave as for the master.
ACS Professional Reducing the bus load HandyTool The zones are defined under Communication. Individual zones can also be disabled via "Command" if they are not being used. This has the advantage of reducing the load on the bus.
3.2 Geographical zone and time switch zone application example RXB with RMB795 To explain the philosophy of the room group, we use the following example. We assume to have a building with 3 floors accommodating a number of companies.
Sport Ltd uses 2 room groups For implementation of the application example, we focus on the floor plan of Sport Ltd.
Settings on the central control unit On the RMB795 central control unit, only the room group, that is, the "Geographical zone (apartment)" can be set. The room and the subzone use a fixed assignment (Room = 1, Subzone = 1). This means that for setting a room group on the central control unit, following applies: Room group = geographical zone (apartment.1.1).
3.3 Procedure for engineering Using the "C3127_Planning and Commissioning Report, Communication Synco 700", the plant and the required communication settings can be represented in an easy-tounderstand way. Proceed as follows: 1. 2. 3. Example Sport Ltd Enter general information, such as plant name, device names, device types, applications, etc. Transfer the device addresses of all bus users and the basic settings of communication from the floor plan.
3.4 Heating and cooling demand zone The building described above is equipped with Synco control equipment on the generation side. Konnex TP1 Controller 1 RMB795 Controller 3 Controller 2 RXB... Controller 4 RXB... Controller 5 RXB...
4 Applications, parameters 4.1 Application selection Most of the RXB Konnex controllers store a number of software applications (e.g. RXB22.1/FC-12 with FNC03 and FNC05). The tool is used to select the required application. ETS Professional and ACS differ greatly in this regard. ETS Professional The tool displays all applications as "devices". The required application is defined by adding a "device".
HandyTool Setting *005 Plant type 1 2 3 4 1 2 3 1 2 1 2 3 4 4.2 Application FNC02 (FC-10) FNC04 (FC-10) FNC08 (FC-10) FNC20 (FC-10) FNC10 (FC-11) FNC12 (FC-11) FNC18 (FC-11) FNC03 (FC-12) FNC05 (FC-12) FNC02 (FC-13) FNC03 (FC-13) FNC04 (FC-13) FNC08 (FC-13) Parameter settings The following chapters describe how to set the parameters, which differs only slightly among the two PC tools. Only the display differs.
5 Room operating modes 5.1 Description The room operating modes available with Desigo RXB are Comfort, Precomfort, Economy and Protection. In addition, there is a frost protection limit, at which, for example, an alarm can be triggered. Each room operating mode has separately adjustable heating and cooling setpoints.
RXB (KNX) application library Room operating modes Occupancy Building use Central S S PPS2 Controller S Temporary comfort mode Room unit DI S Presence detector DI S Window contact Local Prio S Central 3. 3. 3. 2. 1. Effective occupancy S Effective Room operating mode S Room operating mode DI S Window contact Local PPS2 S Temporary comfort mode Room unit DI S Presence detector 3. 3. 3. 3. 1. 1.
5.3 Determine the room operating mode in Desigo (S-mode) In S-mode, the effective room operating mode of the room controller depends on the central Use and Occupancy time schedules and/or on local influences such as window contacts, presence detectors or a room unit. The diagram below shows the priority of these influences and how they are processed by the room controller: Central Local Controller Window contact S DI Prio 1. S Effective room op. mode Building use S 2. S 3.
5.3.1 Local control of room operating mode via a window contact Central Local Controller S Whenever a window is opened, the room controller always switches to the Protection room operating mode, i.e. the heating or cooling output is reduced to a minimum. If a window is opened outside the "buildingin-use" period it is also possible, for example, to arrange for this to trip an alarm in the building automation and control system. Prio 1. DI S 2. S 3. S S S DI 3. PPS2 3.
COThe state of the room controller (result of the logic OR operation) is mapped to the building automation and control system via the following S-mode communication object: Window contact output (Output communication object) Note Flags Type R W C T U Send heartbeat States 1 Yes 0 = Closed 1 = Open 0 1 1 0 1.019 DPT_WindowDoor Master/slave applications Bindings are required in S-mode, in order to transmit the slave window contact status to the master. 5.3.
CO The following S-mode communication object is applicable when using the time scheduler from a building automation and control system: Time schedule Use (Input communication object) Flags Type R W C T U Receive timeout States 0 Yes 0 = In use 1 = Not in use 2 = Protection 1 1 0 5.3.3 Central 0 20.002 DPT_BuildingMode Central and local control of room operating mode based on occupancy Local Controller S Prio 1. DI S 2. S 3.
The presence detector has two possible states: Effective occupancy State Description Occupied • The room is occupied • The room controller switches to Comfort Unoccupied • The room is not occupied • The room controller switches to Economy or Precomfort The table below shows Effective occupancy as a function of the Occupancy time schedule and the presence detector. Principle: "Occupied" takes precedence over “Unoccupied“.
Presence detector The presence detector is connected directly to a digital input on the room controller (see page 142); alternatively an EIB/KNX presence detector connected to the EIB/KNX bus may be used (see diagram below). The two inputs are OR-linked: If one signals presence, presence applies. Since EIB/KNX presence detectors are available from a variety of manufacturers, the name of the S-mode output communication object varies accordingly. Presence detector on DI Room controller RXB...
Effective occupancy (Output communication object) Flags Type Send hearbeat States 20.003 DPT_OccMode Yes R W C T U 1 0 1 5.3.4 1 0 0 = Occupied 1 = Standby 2 = Unoccupied Central control of room operating mode via the Room operating mode time schedule This type of time schedule is not supported in Desigo. If it is nevertheless used, this can cause room controller errors. 5.3.5 Room unit Central Local control of room operating mode with a room unit Local Controller S Prio 1. DI S 2.
The table below shows the effect of the mode of the room controller. /Auto button on the effective room operating Existing effective room op.
The communication object Temporary Comfort mode has two possible states: State Description 1 = Trigger Effective room operating mode is Comfort Has no effect on the Effective room operating mode 0 = Not used Effective room operating mode • The change of effective room operating mode with the Temporary Comfort mode during the building-in-use period (defined by the Use time schedule) • The change of effective room operating mode is event-driven, the key factor being the moment when the communication obj
The resultant Effective room operating mode is also available as 4 digital communication objects: Effective room operating mode Comfort (output communication object) Effective room operating mode Precomfort (output communication object) Effective room operating mode Economy (output communication object) Effective room operating mode Protection (output communication object) Flags Typ L S K Ü A Send Heartbeat Zustände 1 Ja 0 = Aus 1 = Ein 0 5.3.8 1 1 0 1.
Time schedule Use Building in use 06:00 10385D02 22:00 Building not in use Building protection Time schedule Occupancy Rooms 1...
Building in use Use time schedule 06:00 22:00 10385D03 Building not in use Building protection Occupancy time schedule Room 1 and 2 / Auto button on the room unit Room 1 Effective room op. mode Room 1 Occupied Standby 08:00 18:00 Unoccupied Auto 1) 2) 3) 1) 2) 3) Comfort Precomfort Economy Protection mode Presence detector Room 2 Occupied 4) Unoccupied Comfort Effective room op.
5.4 Determine the room operating mode with third-party products (S-mode) In S-mode the effective room operating mode of the room controller depends on the central Room operating mode time schedule and/or on local influences such as window contacts, presence detectors or room units. The diagram below shows how these influences are processed by the room controller, and their priority: Central Local Controller Window contact S Protection mode DI Prio 1. S Effective room op. mode 1.
5.4.1 Local control of room operating mode via the window contact input Central Local Whenever a window is opened, the room controller always switches to the Protection room operating mode, i.e. the heating or cooling output is reduced to a minimum. Controller S DI Prio 1. S 1. 3. S S S DI 3. PPS2 S Effective room operating mode 3. 3. The table below shows the effective room operating mode as a function of the Window contact input.
CO The state of the room controller (result of the logic OR operation) is mapped to the building automation and control system via the following S-mode output communication object: Window contact output (Output communication object) Note Type Flags R W C T U Send heartbeat States 1 Yes 0 = Closed 1 = Open 0 1 1 0 1.019 DPT_WindowDoor Master/slave applications Bindings are required in S-mode so that the status of the window contact connected to the slave can be communicated to the master. 5.4.
5.4.3 Central control of room operating mode via the Use and Occupancy time schedules These time schedules are not supported by third-party S-mode. If they are used nevertheless, this can cause room controller errors. 5.4.4 Presence detector Central and local control of room operating mode based on occupancy Central Local Controller A presence detector detects the presence of people in a room. Prio S 1. DI S 1.
Since EIB/KNX presence detectors are available from a variety of manufacturers, the name of the S-mode output communication object varies accordingly. Room controller RXB...
5.4.5 Room unit Local control of room operating mode with a room unit Central Local Controller S DI Prio 1. S 1. The /Auto button on the room unit can be used like an occupancy button. The room user can use it to switch the HVAC system "on" or "off". 3. S S DI 3. S 3. PPS2 S 3. The room unit is connected to the PPS2 interface on the room controller. It displays the effective room operating mode in a simplified form, and can also be used to change it.
5.4.6 CO Local control of room operating mode via the Temporary Comfort mode input Central Local Controller Prio S 1. DI S 1. 3. S S The communication object Temporary Comfort mode has an effect similar to that of the /Auto button on the room unit. However, the HVAC control system can only be "switched on", i.e. the room operating mode switches to Comfort only. 3. DI S 3. PPS2 3. S Any KNX/EIB switch (pulse switch) can be used for the input: RXB...
The table below shows the effect of the Temporary Comfort mode on the effective room operating mode of the room controller. Existing effective room op.
5.4.8 Third-party (S-mode) examples The following examples show two typical applications of time schedulers in conjunction with local control of the room operating mode. Example 1 Rooms with neither a room unit nor a presence detector The room operating mode in rooms 1…3 of a building is determined by the Room operating mode time schedule. Window contacts are installed in all the rooms. The following conditions are specified: • Overall, the building is in use from 06.00 to 20.00.
• The occupant(s) of Room 1 are working overtime. At 18.00 hours the room operating mode changes to Economy, even if the room unit is set to Auto (1). Comfort mode can now be re-activated with the Auto switch on the room unit (2). Comfort remains active for the pre-defined Temporary Comfort mode period (see page 143). In Protection mode however, the Temporary Comfort period is also overridden and the room operating mode changes to Protection (3).
5.5 Determine the room operating mode with Synco (LTE mode) In LTE-mode the effective room operating mode of the room controller depends on the central Room operating mode time schedule and/or on local influences such as window contacts, presence detectors or room units. The diagram below shows how these influences are processed by the room controller, and their priority: Central (ACS) Central (Synco controller) Local Controller Window contact DI Prio 0. 1. 1. Protection Enable Comfort LTE 2.
5.5.1 Local control of room operating mode via the window contact input Window contact Local Central (ACS) Controller Prio Central (Synco controller) 0. DI Whenever a window is opened, the room controller always switches to the Protection room operating mode, i.e. the heating or cooling output is reduced to a minimum. 1. 1. 2. 3. DI PPS2 Effective room operating mode 3. 3. The table below shows the effective room operating mode as a function of the window contact input.
CO The following LTE-mode communication object is provided for central control: Enable Comfort (input) EnableComfort Timeswitch zone Possible partner-function blocks Known partner devices 110 HVACS HVAC-Mode Scheduler 104 PMC Programme to HVAC-Mode Conversion Siemens: Synco RMB795 The states are: State Description Enabled Priority 3 influences (RoomOperatingMode, presence detector, room unit) are enabled Priority 3 influences are disabled. The effective room operating mode is Economy.
Priorities State Description Room operating mode Comfort Precomfort Economy Protection mode Effective room operating mode of room controller Comfort Precomfort Economy Protection mode • For the room controller, the room operating modes Comfort, Precomfort and Economy are Priority 3 and can therefore be changed later by a presence detector or room unit. • The room operating mode Protection has first priority, and the presence detector and room units are therefore disabled. 5.5.
5.5.5 Room unit Local control of room operating mode with a room unit Local Central (ACS) Controller Prio Central (Synco controller) 0. DI 1. The /Auto button on the room unit can be used like an occupancy button. The room user can use it to switch the HVAC system "on" or "off". 1. 2. 3. DI PPS2 3. 3. The room unit is connected to the PPS2 interface on the room controller. It displays the effective room operating mode in a simplified form, and can also be used to change it.
5.5.6 LTE-Mode Examples The following examples show two typical applications of the time schedule in conjunction with local control of the room operating mode. Example 1 Rooms with neither a room unit nor a presence detector The room operating mode in Rooms 1...3 of a building is determined by the Room operating mode time schedule. Window contacts are fitted in all rooms. The following conditions are specified: • Overall, the building is in use from 06.00 to 20.00.
• The occupant(s) of Room 1 are working overtime. At 18.00 hours the room operating mode changes to Economy, even if the room unit is set to Auto (1). Comfort mode can now be re-activated with the Auto switch on the room unit (2). Comfort remains active for the pre-defined Temporary Comfort mode period (see page 143). In Protection mode however, the Temporary Comfort period is also overridden and the room operating mode changes to Protection (3).
5.6 Determine the room operating mode without a bus (stand-alone) If no bus is connected, the effective room operating mode of the room controller depends on local influences such as window contacts, presence detectors or room units. The diagram below shows how these influences are processed by the room controller, and their priority: Local Controller Window contact DI Prio 1. Presence detector DI 3. PPS2 3.
5.6.1 Window contact Local control of room operating mode via the window contact input Local Controller Prio DI 1. DI 3. PPS2 3. Whenever a window is opened, the room controller always switches to the Protection room operating mode, i.e. the heating or cooling output is reduced to a minimum. The window contact is connected directly to a digital input of the room controller (see page 142).
Effective room operating mode • The change in the effective room operating mode is event-driven, the key factor being the point at which the effective occupancy changes. • The room unit (which is also Priority 3) can cause the effective room operating mode to change again the last command always applies.
The table below shows the effect of the /Auto button on the effective room operating mode of the room controller. Existing effective Display on New effective room Manual operation of room op.
10385D70 Window contact Window open Room 1 Window closed / Auto button on the room unit Room 1 Auto Effective room operating mode Room 1 Comfort 1) 1) 2) 2) 2) 2) Precomfort Economy Protection 10385D71 Window contact Window open Room 2 Window closed 1) 1) Occupied Pres.
6 Setpoint calculation 6.1 Description • Each room controller has 9 different room temperature setpoints: One heating and cooling setpoint for the room operating modes Comfort, Precomfort, Economy and Protection as well as a Frost limit value. • The setpoints – are defined in the tool during engineering. – runtime-adjusted by the communication objects (Desigo, Synco) This does not apply to the Protection setpoints and the frost setpoint (page 32).
6.1.
6.2 Set the setpoints with the tool A tool is used to set the temperature setpoints for the various room operating modes in each room controller. ETS Professional ACS Select Room temperature setpoints.
HandyTool Setpoints See Parameters in the last column of the table below Name Protection cooling setpoint Economy cooling setpoint Precomfort cooling setpoint Comfort cooling setpoint Comfort heating setpoint Precomfort heating setpoint Economy heating setpoint Protection heating setpoint Frost protection limit value *) Basic setting 40 °C 35 °C 28 °C 24 °C 21 °C 19 °C 15 °C 12 °C 5 °C Range 1) 10...40 °C 10...40 °C 10...40 °C 10...40 °C 10...40 °C 10...40 °C 10...40 °C 10...40 °C 2...
In LTE-mode, the central setpoint setting is transmitted via the following communication objects (triplets). Setpoints heating (Input) Setpoints cooling (Input) TempRoomSetpSetHeat TempRoomSetpSetCool Possible partner function blocks Known partner devices Siemens SBT proprietary Siemens: Synco RMB795 Geographical zone STOP Note! Setpoints that have been changed by a tool (e.g. HandyTool) are overwritten by PX-KNX during start-up of the room controller! 6.
CO In a building automation and control system, the central setpoint shift can be influenced via the following S-mode communication objects (triplets): Setpoint shift for heating (Input communication object) Setpoint shift for cooling (Input communication object) Flags Type R W C T U Receive timeout States 0 yes 3 floating point values 1 1 0 0 222.
Function • Comfort: – The Comfort setpoints for heating and cooling are shifted in parallel A . – The original spacing heating – cooling is maintained. Internal correction by controller The room controller corrects the setpoints as follows following a local shift: • Precomfort:: – The values are shifted in parallel to the Comfort values B . – The cooling setpoint cannot be lowered following central shift C . – The heating setpoint cannot be increased following central shift C .
7 Temperature measurement 7.1 Room temperature measurement Sources The value valid for temperature control can originate in various sources: – A room unit via PPS2 7.1.1 – An analog sensor via analog input B1 7.1.2 – Mean value of several sensors 7.1.3 – The bus. 7.1.
The sensors connected to terminal B1 can be tasked with different functions: Parameter setting Room Return air No sensor Only measured value acquisition Supply air (cascade) (RXB2... only) Note ETS Professional Description Room indoor air sensor (can also be used for averaging, see below). Return air sensor (refer also to Section 9.7, "Periodic fan kick") No sensor connected (basic setting, except for FNC08) Uses the signal, see "analog input B1", page 155. Supply air temperature for cascade control.
10385Z14 QAX3... QAA24 PPS2 (CP+, CP-) B1 RXB2... The average value is calculated from the two sensor readings. Notes • In order to determine the average value, the sensor must be configured as a room temperature sensor • The signal is not averaged in the case of return air sensors and KNX sensors. Return air temperature In fan coils with a return air sensor (at B1), the controller must be configured accordingly (see page 132).
Room temperature output (Output communication object) Effective room temperature (Output communication object) Return air temperature output (Output communication object) Note Flags Type R W C T U Send heartbeat Value 1 yes Floating point (°C) 0 1 1 0 9.001 DPT_Value_Temp Invalid temperatures are mapped to the bus as 0 °C.
Subject to the appropriate configuration and integration, the room temperature/return air temperature is read by the controller immediately after a reset. STOP For a Konnex sensor the send heartbeat must be set to "Cyclical sending enabled" Note! The situation is slightly different in LTE mode: Here, each signal has its own specific name, and the room temperature and return air temperature therefore each have their own communication object.
7.3 Supply temperature measurement (FC-13, FNC08 only) Supply temperature can be measured by means of a LG- Ni 1000 sensor (QAP22, QAA24) connected to B2. The value is available on the KNX bus. QAA24 B2 An LG-Ni1000 sensor, type QAP22 or QAA24, may be connected to analog input B2 of the room controller. RXB... STOP Note! Temperature sensor output / input on the Konnex bus • For FNC08 (FC-13), the connected sensor on B2 is automatically used as a supply air sensor.
8 Control sequences 8.1 Fan coils with valve control 8.1.1 4-pipe fan coils - With valve control 10385S01 The applications for 4-pipe fan coils each have a proportional heating and proportional cooling sequence. The RXB2... controllers operate with a PI algorithm optimized for thermal or motorized valve actuators. The RXB39.1 controllers operate with a PI algorithm optimized for proportional valve actuators. (For simplicity, the diagrams below only show the P-control action).
8.1.2 2-pipe fan coils - With valve control 10385S02 2-pipe fan coils have only one proportional control sequence. This may be configured for heating, cooling or changeover operation, as required. The RXB2... controllers operate with a PI algorithm optimized for thermal or motorized valve actuators. The RXB39.1 controllers operate with a PI algorithm optimized for proportional valve actuators. (For simplicity, the diagrams below only show the P-control action).
ETS Professional ACS HandyTool Select Sequences. Select Sequences. Parameter Short name Basic setting *050 Control sequence Cooling Only Parameter Setting Description Control sequence Changeover Cooling only Heating only Changeover signal via KNX bus Cooling sequence only Heating sequence only HandyTool 0 1 2 Actuator type Different applications support different valve actuators, and these do not all require the same number of outputs on the controller.
CO The changeover information must be transmitted to the bus and is integrated via the following communication object: H/C changeover input (Input communication object) Flags Type R W C T U Receive timeout Value 0 yes 0 = Cooling 1 = Heating 1 1 0 0 1.100 DPT_Heat/Cool The following communication object is used in LTE-mode: H/C changeover (Input) Possible partner function blocks ChangeOverStatusWater 342 WCOS Distribution zone, heating Distribution zone, cooling 8.1.
Directly connected valve actuators Different applications support different valve actuators, and these do not all require the same number of outputs on the controller. – Thermal actuators are driven with an AC 24 V PDM signal – Motorized actuators are driven with an AC 24 V 3-position signal. – Electromechanical actuators (motors with spring return) have a special PDM algorithm that ensures that 50 position changes per day are not exceeded. This causes a slower control behavior.
Thermal valve actuators • It is not possible to ensure exact parallel running of more than one thermal valve actuator. If several fan-coils are controlled by the same room controller, preference should be given to motorized actuators. If thermal actuators must nevertheless be controlled in parallel, third-party thermal must be parameterized regardless of manufacture. This applies also if an external power amplifier is used to drive the actuators. • Thermal actuators operate at a raised temperature.
ACS HandyTool Select the valve actuator type from Sequences: Parameter Short name Basic setting *060 Actuator type heating / cooling valve FC-10, FC-11, FC-12 FC-11 / FNC08: FC-13 Settings FC-10, FC-11, FC-12 STE71 1 SSA81 STE72 2 SSB81 STA71 3 SQS81 STP71 4 SSC81 STA72E/STA73 5 SSP81 STP72E/STP73 6 STP72E/STP73 SSP81 SSP61 10 11 12 13 14 Motorized bus Electromech.
Fast actuators For fast actuators, select valve type "Motorized 3rd party devices ". ETS Professional Select Sequences. After selection of third-party devices, a new window opens in which the heating and cooling runtimes can be set.
HandyTool See Parameters in the last column of the table below Motorized and electromechanical actuators. Parameters 4-pipe Running time heating valve Running time cooling valve Offset heating valve Offset cooling valve Basic setting 150 s 150 s 0s 0s Range 0...360 s 0...360 s 0...360 s 0...360 s Resolution 1s 1s 1s 1s HandyTool *061 *062 *071 *072 Parameter 2-pipe Basic setting Range Resolution HandyTool Running time heating / cooling valve 150 s 0...360 s 1s *061 1) Offset heating valve 0s 0...
ACS Select Sequences; Running time …. and Sequences; Positioning signal …. : HandyTool See Parameter number in the last column of the table below 3rd party actuators. Parameters 4-pipe Running time heating valve Running time cooling valve Positioning signal max value Positioning signal min value Note Basic setting 120 s 120 s 10 V 0V Range 0...360 s 0...360 s 0...10 V 0...10 V Resolution 1s 1s 0.1 V 0.
8.1.5 CO Values representing valve actuator positions Valve positions are available in the following S-mode communication objects: Heating coil output (Output communication object) Cooling coil output (Output communication object) Notes Flags Type R W C T U Send heartbeat Value 1 yes 0...100% 0 1 1 0 5.001 DPT_Scaling 0 = 0% 255 = 100% • For Desigo integration: With FNC02 and FNC03 (changeover applications) in S-mode, the valve position is mapped only to heating coil output.
Note The two fields at the bottom of the dialog box only appear if "LTE and S-mode" was selected under Communication. Select Sequences. ACS HandyTool See parameters in the last column of the table below Short name Heating outp bus valve Heating coil outp bus valve Cooling outp bus valve Cooling coil outp bus valve 8.1.
8.1.7 CO Override valve actuators For test purposes, the valve actuators can each be overridden individually via the following communication objects: Heating valve override (Input communication object) Cooling valve override (Input communication object) Note Flags Type R W C T U Receive timeout Value 0 no 0...100% 1 1 0 0 8.
8.2 Fan coils with damper control In FNC20, a single damper actuator is used for control of both heating and cooling. 8.2.1 4-pipe fan coils with damper control (FNC20) In application FNC20, which uses a damper instead of a valve for modulating control of the room temperature, a constant volume of water flows through the two heat exchangers.
Select the damper actuator runtime from Sequences: ACS HandyTool See Parameters in the last column of the table below Parameter name Running time damper heating Running time damper cooling Changeover time damper 8.2.2 CO Basic setting 150 s 150 s 0s Range 0...360 s 0...360 s 0...
8.2.3 CO Overriding the damper actuator For test purposes, the damper actuator can be overridden via the following communication objects: Damper override (Input communication object) Note Flags Type R W K T U Receive timeout Value 0 no 0...100% 1 1 0 0 8.010 DPT_Percent_V16 0= 0% +100 = +100% +32767 = invalid Before the damper actuator can be overridden, “Test” mode must be activated via the communication object Application mode (see page 145).
8.3.1 4-pipe fan-coils with electric reheater The controller operates with a PI algorithm optimized for 2-position / modulating reheaters (RXB2...) or proportional DC 0...10 V reheaters (RXB39.1). For simplicity, the diagrams below only show the P-control action. T Y TR SpC SpH H C YH YC YR D3 B1 Q1 YC YH Q1 T B1 1-step H 100% YH 0% YC OFF SpH 8.3.
Selection of the control mode The control mode must be selected at the engineering stage: heating only, cooling only or changeover Electric reheater with cooling-only or changeover applications The electric reheater also operates with "Cooling only" and "Change-over" in cooling mode. In this case, the heating setpoint (SpH) is used for control.
8.3.3 Electric reheater RXB21.1 (relay) Controller output In the case of the RXB22.1 room controller, the electric reheater is switched directly via output Q44 (max. 1.8 kW resistive). Safety thermostat The controller output of the electric reheater can be disabled locally via a safety thermostat connected to one of the hardware inputs. The alarm input and the way in which it operates can be configured with the tool (see "Digital inputs", page 142).
Enable electric heating (Input) EnableHeat Geographical zone Type of electric heater ETS Professional Possible partner function blocks Known partner devices 115 HVACOPT HVAC Optimizer --- Single-stage or modulating control can be selected in the tool for the electric heater battery. Select Sequences.
Power demand ETS Professional ACS HandyTool If an electric reheater is used, the controller makes the present power demand available on the bus. In order for this to happen, the capacity of the heater battery must be written to the controller via the tool.
The power consumption is mapped to the following communication object: CO Electric output (Output communication object) Flags Type R W K T U Send heartbeat Value 1 yes Floating point (kW) 0 8.3.4 1 1 0 9.024 DPT_Power Electric reheater RXB39.1 (DC 0...10 V plus relay) Controller outputs • DC 0…10V (output YC1): The controller is equipped with a 0…10V output for controlling the electric reheater.
ETS Professional ACS Select Sequences: Select Sequences; Positioning signal max / min electric heater: 103/182 Siemens Building Technologies RXB (KNX) application library Control sequences RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08 2013-06-17
HandyTool See Parameters in the last column of the table below Parameters 2-pipe Positioning sign max el heater Positioning sign min el heater Relay parameter ETS Professional Basic setting 10 V 0V Range 0...10 V 0...10 V Resolution 0.1 V 0.1 V HandyTool *058 *059 To avoid acoustic noise, the relay functionality can be disabled if not needed.
Power demand See "Power demand", page 99. Values representing reheater action See "Desired output", page 99. Central disable signal See page 99.
8.4 Fan-coils with LTHW radiator (FNC18) LTHW radiator applications have a proportional control sequence. The controllers operate with a PI algorithm optimized for thermal or motorized valve actuators. (For simplicity, the diagram below shows only the P-control action.) The radiator sequence can also be used for other heating types, e.g. floor heating. However, the control parameters are not optimized for this. The heater battery of the fan-coil operates in a cascade with the radiator.
ETS Professional Select Sequences, Actuator type heating surface valve: Select Sequences, Act type heating surf valve: ACS HandyTool See Parameters in the last column of the table below For the assignment actuator – Parameter number refer to page 87.
8.4.2 Position values for radiator valve actuators The "position" of the radiator is mapped to the bus. See also section 8.1.5. STOP The Heating surface output communication object must NOT be used for applications for thermal valve actuators to control KNX/EIB valve actuators. With these applications, the communications objects have theoretical valve positions only.
8.4.4 Radiator valve actuator override See also section 8.1.7. CO For test purposes, the radiator valve actuator can be overridden via the following communication objects: Heating surface output override (Input communication object) Note Flags Type R W K T U Receive timeout Value 0 no 00...100% 1 1 0 0 8.
Controller output The heat output calculated by the controller is achieved as follows: LTHW radiators with motorized valve actuators The valve is opened to the heat output value [%].
HandyTool See Parameters in the last column of the table below Parameter for downdraft compensation Outdoor temp.0% valve position Outdoor temp. max. valve position Max. valve position Enabling the function Basic setting 0 °C –10 °C 100 % Range –30...10 °C –30...10 °C 0...100 % Resolution 0.5 K 0.5 K HandyTool parameter *078 *079 1% *080 The following conditions must be fulfilled: – The room controller must be in Comfort mode – The radiator must not be disabled (e.g. by application mode = COOL).
The damper is fully closed if: – the outdoor temperature drops below the frost protection limit (see page 32) – the safty thermostat for the outdoor temperature is activated (see page 142) – the special function "Emergency Heat" is active in Economy mode – the outside air temperature is above the room temperature. Y [%] 10385D18 100 min 0 SpFr SpEmc SpC 8.5.1 TO [°C] Y min TO SpC SpEcm SpFr Position of damper actuator Min.
Select Sequences, Other setpoints: ACS HandyTool See Parameters in the last column of the table below Basic setting 16°C 150s 0% Parameter outside air supply Outdoor temp. min. damper pos. Outside air damper runtime Min. damper position *) Range 10 °C...40°C *) 0...360s 0...100% Resolution 0,5°C 1s 1% HandyTool parameter *073 *074 *075 By temporarily adjusting the setpoint if necessary, the application ensures that there is a differential of at least 1K between the Outside air temp. min. damper pos.
The use of the outside-air damper can only be implemented in conjunction with the RXB21.1 controller. In this case, the AC 24 V 3-position damper actuator is connected to the outputs Y3 and Y4. 8.5.3 Position values for damper actuators The position of the outside air damper is mapped to the bus. CO In S-mode, the following communication object is used for this purpose: Outside air damper (Output communication object) Flags Type R W K T U Send heartbeat Value 1 yes 0...100% 0 1 1 0 5.
8.6 Room supply air cascade control (FNC08) Room supply air cascade control makes it possible to reach the required room temperature very quickly. On the basis of the measured room temperature, the controller calculates a setpoint for the temperature at the air outlet of the fan coil. A limit value can be applied to this temperature to prevent the introduction of uncomfortably cold / warm air into the room.
8.6.1 Parameterizing Basic functions: see sections 8.1.1 through 8.1.7. Minimum supply air temperature and Maximum supply air temperature must be parameterized during engineering. ETS Professional Select Other setpoints: Select Other setpoints. ACS HandyTool See Parameters in the last column of the table below Parameter Minimum supply air temperature Maximum supply air temperature Basic setting 16 °C Range Resolution 10 °C to Comfort heating setpoint 0.
8.6.2 Controller inputs Supply air inputs / outputs The supply air temperature sensor is connected to input B1 / B2 of the controller. The room temperature must be measured with the room sensor installed in the room unit. Temperature sensor Supply air temperature Room temperature Inputs required RXB2... 10385S09 B1 CP+, CP– CO Inputs required RXB39.
9 Fan control 9.1 Description 1 / 2 / 3-speed fan (RXB2...) All fan coil applications incorporate single-speed, two-speed or three-speed automatic fan control. The fan speeds are enabled and disabled via volt-free relay contacts. The controllers operate with an algorithm optimized for thermal or motorized valve actuators for each fan speed. Room unit Certain room units allow the user to select the fan speeds MANUALLY (in Comfort mode only).
The fan runs at fan speed 1 for as long as the heating/cooling valve remains partly open, or in the case of an electric heater, while the heater is in operation. • It is enabled as soon as the controller specifies a valve position or an electric heating output greater than 0. • It is disabled when the controller specifies a valve position or electric heating output equal to 0 and the minimum fan switch-on time has elapsed.
The values have the following effect: Value 0% 0.5...33 % 33,5...66,5 % 67...100 % 100 % Description (required fan speed) 1-stage 2-stage Off Off On 1 On 1 On 2 On 2 3-stage Off 1 2 2 3 If "fan= 0" is commanded via bus, the controller realizes this indirectly by setting the occupancy status to Standby ant thus the effective room operating mode to Precomfort or Economy. The room unit will indicate this as .
9.2 ETS Professional Fan parameter setting 1 / 2 / 3-step Select Fan control, Fan speeds. 9.5 7.1.2 9.7 9.6 Select Fan control: ACS 9.5 7.1.2 9.7 9.6 HandyTool See Parameters in the last column of the table below Paramete Fan speed Fan control Temperature sensor B1 Minimum on time Fan overrun time Periodic fan kick Comfort Periodic fan kick Economy Basic setting 3-speed Auto 6 min 1 min OFF OFF Range (see below) Manual, Auto See 7.1.2 1...10 min 1...10 min 0...89 min ; Off 0...
The following settings can be selected: Parameter Fan speeds (RXB2... only) External fan control 1-speed 2-speed 3-speed Fan control Auto Manual Fan startup behavior Notes Description HandyTool *094 No influence on fans by controller or room unit. The fan is e.g. operated manually at the fan coil. The controller switches on relay Q14 in operating state Comfort, thus allowing for enabling fan operation. 0 Note: For other operating states but Comfort, the fan is enabled by the fan algorithm.
9.3 Description DC 0...10 V fan (RXB39.1) The fan coil applications with RXB39.1 incorporate continuous automatic fan control (DC 0…10 V). In addition the fan can be enabled and disabled via a volt-free relay contact. Controller RXB39.1 Controller outputs (fan) Output characteristic Outputs G0 / YC3 Q33 / Q34 DC 0…10 V signal for the fan Enable relay for the fan The output characteristic of the fan signal (0…10V) is defined via parameters P150 and P151. Output signal YC3 10 V E.g. 1: Pos.
Function The fan speed is controlled by a PI controller depending on the control deviation of the valve or reheater. The fan starts running at the min speed when the valve or reheater demand exceeds 4%; it is deactivated when the demand is 0% (hysteresis). Control strategy fan in sequence Control strategy fan in parallel When the valve or/and electric reheater is fully open AND the room temperature exceeds the fan offset (P162, P163), the fan output signal grows up to the max. value (P152, P154).
Sequence and parallel Fan Valve Speed XPFanH OfsFanH 100% OfsFanC XPFanC = = SmaxC SmaxH SminH 0% SminC SpHCmf SpCCmf TR Fan coils with return air sensor If the fan coil is equipped with a return air sensor, the fan has to run at least periodically in order to measure a correct temperature. This running is activated by means of the sensor selection (return air sensor). The fan running time and period can be defined, see "Periodic fan kick", section 9.7.
9.3.3 Room unit (RXB39.1/FC-13 only) Certain room units allow the user to toggle the room operating mode and automatic fan operation or manual selection of the fan steps (in Comfort mode only). The reaction of the controller upon the user's inputs can be parameterized in the applications of FC-13.
9.3.4 CO Values representing fan speed Besides operation via a PPS2 room unit, he fan can also be operated via the KNX bus. In S-mode, control is shared between two communication objects: – Fan command value – Enable fan command value (activates input Fan command value). When Enable fan command value is disabled, the controller controls the fan automatically, and the Fan command value input is disabled.
The following example illustrates the effect of the commanded fan value via KNX bus on the room units's display: Command (from KNX bus) X = 0% QAX LED / cursor position Heating: I 0% < X <=23% Cooling: 0% < X <=33.5% Heating: II 23% < X <=50% Cooling: 33.
9.4 ETS Professional Fan parameter setting DC 0...
ACS HandyTool Select Fan control: See Parameters in the last column of the table below Parameter Basic setting Range Resolution HandyTool Output characteristic Positioning signal max fan Positioning signal min fan 10 V 0V 0...10 V 0...10 V 0.1 V 0.1 V *150 *151 100 % 20 % 100 % 20 % 20 % 20 % 20 % 100 % 100 % 0.0 K 0.0 K 1.0 K 1.0 K 10 min 10 min Enabled (1) 0...100 % 0...100 % 0...100 % 0...100 % 0...100 % 0...100 % 0...100 % 0...100 % 0...100 % 0...3 K 0...3 K 0.5...5 K 0.5...5 K 0...
Parameter Parameters with el heater Fan overrun time Fan overrun speed min Other parameters Fan control (details see below) Minimum on time Periodic fan kick Comfort & Precomfort Periodic fan kick Economy Basic setting Range Resolution HandyTool 1 min 20 % 1...10 min 10...100 % 1 min 1% *098 *159 Auto Manual, Auto 6 min OFF OFF 1...10 min 0...89 min ; Off 0...359 min ; Off Temperature sensor B1 / B2 See section 7.1. Fan Parameters 168...172 for the room unit See section 12.
9.7 Return air sensor Periodic fan kick If the room temperature is measured with a return air sensor in the fan coil (connected to input B1, see Section 7), the fan must be switched on to ensure that the effective room temperature is measured correctly. The function "Periodic fan kick" is used for this purpose. From version V2.36, a reduced functionality (without time values for Comfort and Economy) is available even if no return air sensor is parameterized.
10 Master/slave 10.1 Description Example of a master/slave configuration: Several controllers are installed in an openplan office. One controller (the master) measures the room temperature and controls the other controllers (slaves) via the KNX bus. This ensures that it will be possible to subdivide the room into smaller rooms, without the need to change the wiring.
10.
10.2.1 Window switch (S-Mode) For master/slave mode, only the master's window switch is evaluated without special measures, which also influences the slave controllers. If another window switch is also connected to the slave, it is NOT considered unless you create the following binding: Master Slave Window contact Input Window contact Output DI DI 10385Z118en This binding ensures that both controllers react when a window is opened.
10.3 LTE mode with zones The master/slave configuration is also possible in LTE mode. However, you do not need to create the individual bindings, but instead define the master/slave zone. Here too, the following applies: The slaves must be controlled by only one master, and master/slave bindings are only possible between controllers with the same version (ASN) featuring the same applications and settings. ETS Professional Select Master / Slave: Example Room Geogr.
HandyTool Parameter Short name Basic setting *021 *022 *023 *024 Master/Slave Master/Slave zone (apart.) Master/Slave zone (room) Master/Slave zone (subzone) Master 1 –1 (out of service) 1 Parameter *021 Master/Slave Setting Master Slave HandyTool 1 0 10.3.1 Window switch (LTE mode) For master/slave mode, only the master's window switch is evaluated without special measures, which also influences the slave controllers. Window switches on the slaves are NOT considered. 10.3.
10.4 Room units in master / slave configurations Peripheral functions The room controllers and room units can be configured as master or slave devices. A number of rules must be adhered to in this process. When more than one room unit is used in a master/slave configuration, all such room units must be of the type with a button for setpoint adjustment. In the case of room units with a mechanical setpoint adjuster, only one room unit may be connected.
11 ETS Professional General and central functions The following functions are enabled or configured via General functions or Central functions. See Section 3 11.1 11.2 11.3 11.4 11.5 11.8 11.10, 11.14 11.
ACS The following functions are enabled or configured under General or Central functions. 11.2 11.3 11.4 *) 11.16 *) Room number and Device name do not influence the application; they are used only for plant documentation purposes. We recommend to use this feature. HandyTool The general and central functions are set with parameters 117 – 137. For detailed information, refer to the individual sections.
11.1 Send heartbeat and receive timeouts In a KNX network, S-mode and LTE mode communication objects can be exchanged between individual devices. The Receive timeout defines the period of time within which all the communication objects requested from a device must have been received at least once. If a communication object is not received within this period, a predefined value is used and an error message is generated. This ensures that interruptions in communication are identified at an early stage.
11.2 Digital inputs The following volt-free contacts can be connected to digital inputs D1 and D2: • Presence detector or window contact (for details of this function see Section 5). • Safety thermostat electric heating coil / reheater (for details of this function, see page 96). • Safety thermostat outdoor temperature (for details of this function, see page 109).
The min. fan speeds for Comfort, Precomfort, Economy and Protection (P153, P156, P157 and P158, see page 129) must be set to a value that guarantees that the full heat of the electric heater can be dissipated. WARNING 11.3 Temporary Comfort mode If the room controller is set to Economy mode and the associated room unit is switched to Auto (Comfort), the controller maintains Comfort mode for the period defined by the temporary occupancy override time (veto) and then switches to Economy.
CO The heating or cooling demand can be evaluated via the following S-mode communication object. Energy demand room (Output communication object) Flags Type R W C T U Send heartbeat Value 1 yes 0 1 1 0 6.001 DPT_Percent_V8 –100...100% : (-128...+127) –100% = Full heat +100% = Full cool In LTE mode the energy demand is determined by two signals: Heating coil energy demand (Output) EnergyDemAH Distr.
11.7 CO Special functions The special functions described in sections 11.8 ff are triggered by the following Smode communication object: Application mode (Input communication object) Flags Type R W C T U 0 1 1 0 0 Receive timeout yes 20.
STOP ETS Professional Go to the Functions menu for the disable feature. HandyTool See parameters in the last column of the above table. Note! The special functions are disabled if the user requires manual (P093) or reduced (P168) operation on the room unit. 11.8 Boost heating (Morning Warmup, 2) This function is used to raise the temperature in a room as quickly as possible to the Precomfort heating setpoint at the end of the night setback period. Objective: Preheat the room for heating.
Enabling the function The following condition must be fulfilled: – – – – FNC must have an outside air damper. The outside air damper must not be disabled The room controller must be in Economy mode. The outside air temperature must be lower than the room temperature (Hysteresis = 1K) The function can be disabled in the room controller by means of P138 or the ETS tool, see central functions, page 139.
11.11 Test mode (Test, 7) The following override functions are used to commission the controller and for service purposes, e.g. to test a valve actuator. Test mode The controller must first be switched to HVAC test mode by transmitting the value 7=TEST via Application mode. To quit test mode, first transmit 6=OFF, and then 0=AUTO. Aggregates In test mode, the valves, air dampers, electric heating coils and fans can be set to defined values via KNX bus signals.
Terminating the function – The function is disabled via the building automation and control system – When the room temperature rises above the Protection setpoint. 11.13 Rapid ventilation (Fan only, 9) This function (formerly Air flush) is only used in Precomfort and Economy room operating modes. The function is NOT supported by RXB39.1 The aim is to flush the building with as much outside air as possible to renew the room air.
11.14 Free cooling (Freecool, 10) This function is used to precool rooms to the Comfort cooling setpoint, in readiness for normal occupancy. It uses both fan and cooling coil. This function is meaningful only if low-tariff energy is available. During occupancy (Comfort / Precomfort) normal mode applies. 3-step fan DC 0...
11.15.1 S-mode CO In S-mode, the above described alarms are provided as a common alarm. The alarm message is mapped to the following S-mode output communication object: Common alarm (Output communication object) Note Flags Type R W C T U Send heartbeat States 1 yes 0 = No alarm 1 = Alarm 0 1 1 0 1.005 DPT_Alarm As soon as the cause of the alarm ceases to exist, the alarm message disappears.
EnableAlarmInfo (Input) Possible partner function blocks Siemens Synco RMU710 / 20 / 30, RMH760, RMB795, RMS705 EnableAlarmInfo Broadcast Display on a Synco device: Known partner devices Error code Short name 4910 RXB room temp.
11.17 Free inputs/outputs In a building automation and control system, the free I/Os can be used to interrogate switch states, for example, or for direct switch control of another device over the network. However, these functions are not suitable for time-critical processes (<1 s). Free inputs can be defined as "open" or "closed" (see 11.2). If not already in use, the following inputs and outputs can be used freely: RXB21.1/FC-10 Application FNC02 FNC04 FNC08 FNC20 RXB21.
11.17.1 Digital inputs on the KNX bus RXB... Room controller CO 10385Z19en D1 Digital input 1 D2 Digital input 2 The following S-mode input and output communication objects are used when taking advantage of spare inputs and outputs: Digital input 1 (Output communication object) Digital input 2 (Output communication object) Digital input 3 (Output communication object) Digital input 4 (Output communication object) Flags Type R W C T U 1 0 1 1 0 1.
11.17.3 Mapping the sensor B1 / B2 to the Konnex bus RXB... Room controller B1 10385Z201en Analog input B1 Temperature sensor B1 / B2 can also be connected to the bus in S-mode as a universal temperature (e.g. outside temperature). To do this, the temperature sensor must be parameterized as "only meas value acquisition" (see page 75.) Analog input B1 / B2 (Output communication object) Flags Type R W C T U 1 0 1 1 0 Send heartbeat 9.001 States Yes DPT_Value_Temp 11.
12 ETS Professional Room unit Select Room unit: Select Room unit: ACS HandyTool See Parameters in the last column of the table below 156/182 Siemens Building Technologies RXB (KNX) application library Room unit RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08 2013-06-17
Parameters (Description see below) Measured value correction Setpoint adjustment range Local Comfort mode Room unit (Handy tool: fixed as "With LCD") Temperature unit (only room units with LCD) Standard display (only room units with LCD) Setpoint display (only room units with LCD) Fan function standby Fan speed user defined User fan speed 3 User fan speed 2 User fan speed 1 Parameters for fan control Sensor correction Basic setting 0.
Displaying heating and cooling symbols (ETS only) The display of the heating and cooling symbols can be enabled or disabled. Note that this applies only to room units with an LCD display. Symbols: Cooling sequence active Heating sequence active Parameter Heating/cooling symbol display Selecting the temperature unit Description Heating and cooling symbols are displayed Basic setting Enabled The room temperature can be displayed either in Celsius (°C) or Fahrenheit (°F).
Temperature display in case of a setpoint shift In room units with an LCD, it is possible to define what is to be displayed in the event of a setpoint shift. Parameter Setpoint display Relative Absolute LCD display (only room units with LCD). Shift value e.g. +3.0K (basic setting) Effective temperature setpoint, e.g. 23.0 °C (Mean value between heating and cooling setpoint).
Reset 13 KNX information 13.1 Reset and startup response A reset is initiated under the following circumstances: Processor failure(e.g. watchdog). After a power failure. After a bus power failure. Upon completion of a self test (using the communication object "StatusRequest"). Via ETS (without a startup delay): – After the download of the physical address. – After the download of the parameters. – Via ETS (menu Commissioning, Reset). • After parameter setting in ACS.
13.3 Startup delay After a reset, it takes up to 5 minutes for all the connected room controllers to restart. This is designed to avoid overloading the mains power supply when restarting. At the same time, it reduces the load on the KNX network, as not all controllers transmit data at the same time. The delay is determined by the controller's device address. 13.
13.5 S-mode communication objects for FNC 13.5.
13.5.2 S-mode output communication objects Flags: R Read W Write C Communication Name Alarm info Analog input B1 / B2 Common alarm.
HandyTool parameters by number d S d d d d d d d d S S S S S S S S X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 8) X X X 8) X X X X X 1) X X 2) X X X X X X 8) X X 8) FNC12 X X X X X X X X X X X X X X X FNC08 P P X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 8) 8) X X X X X X X X X X X X X X X X X X X X X X X X X X FNC04 063 064 066 068 069 070 071 072 P P P P P P S S S S S S S S S S S S S S S S S S S S S S S X X X X X X
FNC04 FNC08 152 145 130 099 101 103 105 FNC03 137 138 150 098 FNC02 145 097 FC-13 FNC05 136 094 095 096 X X X FC-12 FNC03 108 109 110 113 114 115 116 117 119 120 123 124 127 128 131 132 134 135 122, 131 122 121 121, 131 121, 131 121, 131 104 157 157 58, 157 158 158 159 142 142 142 142 143 143 143 139 139 141 141 143 143 145 145 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
S S S S S S S X X X X X X X X X X X X X X X X X X X X X X d d d d d d d d d d S S S S S S S S S S X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X P X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X FNC05 FNC03 d d d d d d d X X X X X FNC18 X Fan speed user defined User fan speed 3 User fan speed 2 User fan speed 1 Enable fan relay Application set Application version Operating system version KNX interface version Device state FNC12
HandyTool parameters sorted alphabetically 160 X X X X X X X X X X S S S S S S S S S S S S S X X X X X X X X X X X X X X X X 5) X X X X X X X X X X X X X FNC08 X X X X X X FNC04 X X X FNC03 X X X FNC02 X X X FNC05 X FNC03 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X FC-13 FNC18 X FC-12 FNC12 159 094 154 155 157 152 153 156 158 169 161 S S S S S S S S S S S S FNC10 24 24 24 098 FNC08 008 009 010 168 FNC04 135 143 139 155 1
d d S S X X X X X X X X X X X X S S S S S S S S S S S S S X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 8) X X X X X X X X X X X X X X 239 105 155 58, 157 137 137 137 137 116 111 157 113 121 116 145 143 89 Master/slave.
FNC12 FNC18 FNC03 FNC05 FNC02 FNC03 FNC04 FNC08 158 24 24 24 143 130 130 159 159 159 FNC10 108 011 012 013 117 166 167 170 171 172 061 FNC20 064 074 127 110 103 109 092 141 152 71 139 89, 90, 95 89, 90, 95 107 113 141 159 157 158 76 FNC08 128 137 040 123 062 FC-13 FNC04 71 71 71 71 145 FC-12 FNC02 032 035 030 037 136 FC-11 S = Service (Mode 6) ("Ext. param.
FNC HandyTool enumerations CLC / RAD 13.8 Physical address X X 5 Plant type X X 6 Communications mode. X X 0 = S-Mode 1 = FNC02 1 = FNC10 1 = FNC03 1 = FNC02 8 - 10 Geographical zone X X 1 = S+LTE-M 2 = FNC04 2 = FNC12 2 = FNC05 2 = FNC03 11 -13 Time switch zone X X 3 = FNC08 3 = FNC18 X 4 = FNC20 No. Parameter 1-3 14 Heat distribution zone air heater. 15 Refrig distribution zone air cooler.
13.9 Data point type description Instead of the previously referenced EIS data types, this document now makes reference to the new Konnex data point types. Where possible, the tables which follow do include a reference to the corresponding EIS type. Data point types ID 1.001 Name DPT_Switch Format B(1) Unit Bit 1.003 DPT_Enable B(1) Bit 1.005 DPT_Alarm B(1) Bit 1.017 DPT_Trigger B(1) Bit 1.018 DPT_Occupancy B(1) Bit 1.019 DPT_Window_Door B(1) Bit 1.100 DPT_HeatCool B(1) Bit 5.
ID 219.001 Name DPT_AlarmInfo 222.100 DPT_TempRoom SetpSetF16[3] 222.101 DPT_TempRoom SetpSetShiftF16[3] Format U(8)U(8) N(8)N(8) B(8)B(8) F(16)F(16)F(16) Unit -- Range/Coding Alarm description Corresp.
14 FAQs Question: What happens if the parameter download process is interrupted? (power failure, bus failure etc.) Answer: The parameter set loaded into the controller will be incomplete. The controller will not start up properly. For example, the fan may run but the valves do not open. You will have to download the parameters again.
Question: Why does a controller with thermal valves not respond immediately when it is enabled in the plant graphics in the ACS view and in the Desigo graphics? Answer: After start-up, the thermal valves are preheated first. This is not shown in the plant graphics. However, if the room temperature is outside the dead band during this period, the fan switches to Speed 1. Question: Why doesn’t the master/slave binding work? Answer for LTE mode: Master/slave zones must be identical for master and slave.
15 Integrate RXB in Desigo/Synco Combinations of RXB controllers with Synco and a Desigo integration are possible and certainly make sense. However, certain combinations must be excluded; for others, certain boundary conditions must be respected. In the following sections the most common combinations are presented. Key Display Time scheduler 10385D69 Heating demand Cooling demand 15.
15.2 Case 2: Integration into Desigo • Communication: – between controllers – with Desigo: • RXB display: • RXB time scheduler: • Energy demand: S-Mode Individual addressing or S-Mode Desigo from Desigo to Desigo DESIGO INSIGHT ALN PXC... PXC...
15.3 Case 3: Display in Desigo, with shared Synco time scheduler • Communication: – between controllers – with Desigo: • RXB display: • Synco display: • RXB time scheduler: • Energy demand: STOP Important note LTE mode via zones Individual addressing or S-Mode Desigo Desigo from Synco to Synco The Desigo time scheduler must be disabled by a specialist. Reason: Integration by means of individual addressing treats the time scheduler and display as one package. They subsequently need to be separated.
15.4 Case 4: Display in Desigo/Synco, with shared Synco time scheduler • Communication: – between controllers – with Desigo: – with ACS: • RXB display: • Synco display: • RXB time scheduler: • Energy demand: STOP Important note LTE mode via zones Individual addressing or S-Mode Individual addressing Desigo and ACS Desigo and ACS from Synco to Synco • The Desigo time scheduler must be disabled by a specialist. • In theory simultaneous display via Desigo and Synco is possible.
15.5 Case 5: Display in Desigo, and separate time schedulers • Communication: – between controllers – with Desigo: • RXB display: • Synco display: • RXB time scheduler: • Energy demand: STOP Important note LTE mode via zones Individual addressing or S-Mode Desigo Desigo from Desigo to Synco • The RXB controllers use the Desigo time scheduler • The Synco controllers need a local Synco time schedule • The two schedules must be kept synchronous DESIGO INSIGHT ALN PXC... PXC...
15.
15.7 Case 7: Separate display, and shared Synco time scheduler • Communication: – between controllers – with Desigo: – with ACS: • RXB display: • Synco display: • RXB time scheduler: • Energy demand: STOP Important note LTE mode via zones Individual addressing or S-Mode Individual addressing Desigo ACS from Synco to Synco The Desigo time scheduler must be disabled by a specialist. DESIGO INSIGHT ALN PXC... PXC... ACS7..
16 Working with different tools It is possible to prepare the RXB controllers in the office by setting the parameters in advance, so that only the physical address has to be entered on site. The HandyTool contains a “limited” parameter-setting option which can be used for this purpose. The preparatory work would then probably be carried out with ACS or ETS rather than with the HandyTool. Special caution is required (in relation to data consistency) when using more than one tool.