Assortment / System Description
10
Applications
The scope of the RXB controllers is defined by the pre-programmed application
modules.
The following is an overview of the various applications and associated controllers.
The controllers are shipped from the factory pre-programmed with a set of applications.
The required application is then enabled with a tool (ETS, ACS or the "HandyTool").
Due to the fact that the applications are largely pre-defined, engineering simply involves
the definition of a small number of parameters, e.g.:
• 2-position or 3-position control of valves and actuators (depending on application)
• Temperature setpoints
• Manual or automatic fan control
Fan coil systems (examples)
Appl.
Description
Controller
FNC02
Two-pipe system with change-over
RXB21.1 / FC-10, RXB39.1 / FC-13
FNC04
Four-pipe system
RXB21.1 / FC-10, RXB39.1 / FC-13
FNC08
Four-pipe system with room supply air cascade control
RXB21.1 / FC-10, RXB39.1 / FC-13
FNC20
Four-pipe system with control of a single damper
RXB21.1 / FC-10
FNC10 Two-pipe system with change-over outside air damper RXB21.1 / FC-11
FNC12 4-pipe system with outside air damper RXB21.1 / FC-11
FNC18
Two-pipe system with change-over and radiator
RXB21.1 / FC-11
FNC03
Two-pipe system with change-over and electric heater
RXB22.1 / FC-12, RXB39.1 / FC-13
FNC05 Four-pipe system with electric heater RXB22.1 / FC-12
Common functions
• Window contact, presence detector, four operating modes
• Manual fan control via room unit
• Automatic 3-speed or continuous fan control
• Options with two-pipe systems: Heating only, cooling only or
changeover via KNX bus
For a detailed description of the applications available, refer to the Applications library,
CM110385 und CM110672.
Chilled ceiling and radiator (example)
Appl.
Description Controller
CLC01
Chilled ceiling
RXB24.1 / CC-02
CLC02 Chilled ceiling and radiator RXB24.1 / CC-02
RAD01
Radiator
RXB24.1 / CC-02
Common functions
• Window contact, presence detector, four operating modes
• Dew point sensor (CLC)
• Downdraft compensation (radiator)
For a detailed description of the applications available, refer to the Applications library,
CM110384 und CM110671.
01577
M
T
T
Raum-Controller
01578
T
Raum-Controller