User Manual
9/10
Siemens Non-communicating room controllers CA2N3882en_02
Building Technologies RXA29.1 2012-08-28
Parallel connection of a number of thermic valve actuators to output Y1 using the UA1T
power amplifier.
The same principle applies to outputs Y2 … Y4. Note that the simultaneous load on
outputs Y1 … Y4 must not exceed 9.5 VA (power consumption at input X1 of the UA1T:
0.5 VA)
1
2
3
4
NS
LS
COM
X1
AC 24 V
Y1.1
Y1.1
70206
6
7
Y1
G
Y1
G0 G
8
7
6
5
COM
Y1
COM
Y1
N2
1
2
3
4
NS
LS
COM
X1
Y1.1
Y1.1
8
7
6
5
COM
Y1
COM
Y1
N2
N1
N1 RXA29.1
N2 UA1T (see data sheet CA2N3591)
Y1 AC 24 V thermic valve actuator
Y1.1 AC 24 V thermic valve actuator (max. 2 STP72E actuators per Y1 output on the UA1T)
– The UA1T requires an AC 24 V supply voltage
– The UA1T is not suitable for the connection of 3-position actuators.
Connecting a
power amplifier
Notes