User Manual
8/14
Siemens Non-communicating room controllers CA2N3881en_02
Building Technologies RXA20.1, RXA21.1, RXA22.1 2012-08-28
Connection terminals and operator controls
00600 a
12345678 10
M
D1
GND
D2
Y1
G
Y2
B1
12
PPS2
T
19 21 25 26
N
L
Q13
Q14
N
5(4) A
14 15 16
CP-
CP+
M/S
9
X2
D3
T
0...10 V
56784321
ON DIP
910
S1...10
R1
21
L
19
AC 230 V
11 12 13
G
Measured value inputs
B1 1 Measured value input for LG-Ni 1000 sensor or setpoint adjuster
M 2 Measured value input ground
X2 3 Configurable input for LG-Ni 1000 sensor, setpoint adjuster or 0…10 V signals
Signal inputs
D1 4 Signal input (window or clock)
GND 5 Signal ground
D2 6 Signal input (occupancy)
D3 7 Changeover input
Triac outputs
Y1 8 AC 24 V, 0.5 A switching output
G 9 AC 24 V actuator supply
Y2 10 AC 24 V, 0.5 A switching output
Device bus
M/S 14 Master/slave connection
CP– 15 Ground for PPS2 and M/S
CP+ 16 PPS2 (room unit)
Power supply
N 19 Neutral conductor
L 21 Phase conductor AC 230 V +/- 10 %
Relay outputs
Q13 25 Lead wire for Q14
Q14 26 Normally-open contact max. AC 250 V, 5 (4) A
Operator controls
S1...10 DIP switch for configuring the room controller.
R1 Potentiometer for setpoint reset and test purposes.
STOP
Caution Observe the technical data for the relay output: max. AC 250 V, 5 (4) A
Local installation regulations must be observed.
RXA20.1
Important