User Manual

10/14
Siemens Non-communicating room controllers CA2N3881en_02
Building Technologies RXA20.1, RXA21.1, RXA22.1 2012-08-28
Connection terminals and operator controls
3881Z02
12345678 10
M
D1
GND
D2
Y1
G
Y2
B1
12
QAX...
T
25 26 27 28
Q13
Q14
Q24
Q34
5(4) A
14 15 16
CP-
CP+
M/S
9
X2
D3
T
0...10 V
R1
22 23
24
N.C.
Q44
10 A
56784321
ON DIP
910
S1...10
19 21
N
L
N
21
L
19
AC 230 V
11 12 13
G
Q43
Measured value inputs
B1 1 Measured value input for LG-Ni 1000 sensor or setpoint adjuster
M 2 Measured value input ground
X2 3 Configurable input for LG-Ni 1000 sensor, setpoint adjuster or 0…10 V signals
Signal inputs
D1 4 Signal input (window or clock)
GND 5 Signal ground
D2 6 Signal input (occupancy)
D3 7 Changeover input
Triac outputs
Y1 8 AC 24 V, 0.5 A switching output
G 9 AC 24 V actuator supply
Y2 10 AC 24 V, 0.5 A switching output
Device bus
M/S 14 Master/slave connection
CP– 15 Ground for PPS2 and M/S
CP+ 16 PPS2 (room unit)
Power supply
N 19 Neutral conductor
L 21 Phase conductor AC 230 V +/- 10 %
Relay outputs
Q13 25 Shared contact for Q14, Q24 and Q34
Q14 26 Normally-open contact, max. AC 250 V, 5 (4) A (Stage 1)
Q24 27 Normally-open contact, max. AC 250 V, 5 (4) A (Stage 2)
Q34 28 Normally-open contact, max. AC 250 V, 5 (4) A (Stage 3)
N.C. 22 Not connected
Q43 23 Lead wire for Q44
Q44 21 N/O contact AC max. 250 V, 10 A...(electric heating coil)
Operator controls
S1...10 DIP switch for configuring the room controller.
R1 Potentiometer for setpoint reset and test purposes.
STOP
Caution Observe the technical data for the relay outputs:
max. AC 250 V, 5 (4) A or 10 A
Local installation regulations must be observed.
RXA22.1