Data Sheet for Product

6
Siemens
A6V10733750_en--_d
Smart Infrastructure
2020-07-22
NTC 100k
Temperature range
-10...+130 °C
Temperature
Accuracy
-10...0 °C
1.5 K
0...50 °C
1 K
70 °C
1.5 K
90 °C
2.1 K
100 °C
2.9 K
Wiring diagram
Please refer to NTC 10k.
PT 1000 (3850 ppm / K)
Temperature range
-50...+150 °C
Temperature
Accuracy
-50...150 °C
1 K
25 °C
0.5 K
Wiring diagram
Please refer to NTC 10k.
LG Ni 1000 (5000 ppm / K)
Temperature range
-50...+150 °C
Temperature
Accuracy
-50...°C 150 °C
1 K
25 °C
0.5 K
Wiring diagram
Please refer to NTC 10k.
0 (4)...20 mA
Accuracy
+/- 1% F.S. (internal measurement of re-
sistance 440 Ω)
Wiring diagram
(for reference only)
No internal over-current protection!
Universal input