Basic Documentation

13 / 26
Siemens RWD Primary Controls Modbus Interface CB1P3099en_01
Building Technologies Modbus Operation 27.10.2009
Read RWD68 parameter (ADDR = 30055, 30056) called RWDAPP with Modbus
ADDR = 0054, 0055:
SEZ50MB
Device Address
Function Code
Modbus Address Data Length CRC16 Check
Send
F7 04 00 36 00 00 or 01
85 53
WRONG INFO
SEZ50MB
Device
Address
Function
Code
Exception Code CRC16 Check
Respond
F7 84 14 A3 3D
Write RWD32S parameter (ADDR = 00001) called bFrostEnable with Modbus ADDR
= 0000:
SEZ50MB
Device Address
Function Code
Modbus Address Value CRC16 Check
Send
F7 05 00 00 FF FF 98 AC
WRONG INFO
OR
SEZ50MB
Device Address
Function Code
Modbus Address Value CRC16 Check
Send
F7 05 00 00 00 FF 98 AC
WRONG INFO
SEZ50MB
Device
Address
Function
Code
Exception Code CRC16 Check
Respond F7 85 03 E2 A3
Note: Only two possibilities for Value column writing a 0 using Value = 0x 00 00
or writing a 1 using Value = 0x FF 00
Write RWD68 parameter (ADDR = 40117, 40118) called SP3day with Modbus ADDR
= 0116, 0117:
SEZ50MB
Device Address
Function Code
Modbus Address Data Length Byte
Count
Send
F7 10 00 74 00 01 To below
WRONG INFO
Data
Length
Byte
Count
Status
(IEEE 754 format)
CRC16 Check
From
Above
04 41 E8 00 00
(SP3 day setpoint 29 °C)
7C FB
OR
SEZ50MB
Device Address
Function Code
Modbus Address Data Length Byte
Count
Send
F7 10 00 74 00 02 To below
Data
Length
Byte
Count
Status
(IEEE 754 format)
CRC16 Check
From
Above
05 41 E8 00 00
(SP3 day setpoint 29 °C)
7C FB
WRONG INFO
SEZ50MB
Device
Address
Function
Code
Exception Code CRC16 Check
Respond F7 90 14 AC 3D
Function Code 0x04 à
(Error Message)
Function Code 0x05 à
(Error Message)
Function Code 0x10 à
(Error Message)