User guide

Chapter 3
Device Management
RUGGEDCOM ROS
User Guide
60 Configuring IP Services
8 9
7
6
5
4
3
2
1
Figure 25: IP Services Form
1. Inactivity Timeout Box 2. Telnet Sessions Allowed Box 3. Web Server Users Allowed Box 4. TFTP Server Box 5. Modbus
Address Box 6. SSH Sessions Allowed Box 7. RSH Server Box 8. Apply Button 9. Reload Button
2. Configure the following parameter(s) as required:
Parameter Description
Inactivity Timeout Synopsis: 1 to 60 or { Disabled }
Default: 5 min
Specifies when the console will timeout and display the login screen if there is no user
activity. A value of zero disables timeouts. For Web Server users maximum timeout
value is limited to 30 minutes.
Telnet Sessions Allowed Synopsis: 0 to 4
Default: 0 (controlled version) or 4 (non-controlled version)
Limits the number of Telnet sessions. A value of zero prevents any Telnet access.
Web Server Users Allowed Synopsis: 1 to 4
Default: 4
Limits the number of simultaneous web server users.
TFTP Server Synopsis: { Disabled, Get Only, Enabled }
Default: Disabled
As TFTP is a very insecure protocol, this parameter allows user to limit or disable TFTP
Server access..
DISABLED - disables read and write access to TFTP Server
GET ONLY - only allows reading of files via TFTP Server
ENABLED - allows reading and writing of files via TFTP Server
ModBus Address Synopsis: 1 to 255 or { Disabled }
Default: Disabled
Determines the Modbus address to be used for Management through Modbus.
SSH Sessions Allowed (Controlled
Version Only)
Synopsis: 1 to 4
Default: 4
Limits the number of SSH sessions.
RSH Server Synopsis: { Disabled, Enabled }
Default: Disabled (controlled version) or Enabled (non-controlled version)