User guide

RUGGEDCOM ROS
User Guide
Chapter 5
Setup and Configuration
Configuring the Mirrored Bits Protocol 141
Parameter Description
Default: In
The Call direction for TCP Tranport.
In: accepts an incoming connection.
Out: places an outgoing connection
Both: places an outgoing connection and waits for as incoming connection (both
directions).
Max Conns Synopsis: 1 to 64
Default: 1
The maximum number of allowed incoming TCP connections.
Loc Port Synopsis: 1 to 65535
Default: 21001
The local IP port to use when listening for an incoming connection or UDP data.
Rem Port Synopsis: 1 to 65535
Default: 21000
The remote TCP port to use when placing an outgoing connection.
IP Address Synopsis: ###.###.###.### (where ### ranges from 0 to 255) | { <empty string> }
Default: <empty string>
Defines the IP address based on the following:
For outgoing TCP connection (client), this is the remote IP address to communicate
with.
For incoming TCP connection (server), this is the local interface IP address to listen
to for the local port for connection request. If an empty string is configured, the IP
address of the management interface is used.
When both outgoing and incoming connections are enabled (client or server), this is
remote IP address to use to place an outgoing TCP connection request or from which
to accept calls
For UDP transport, this is the IP address of the interface to listen to for UDP
datagrams.
Link Stats Synopsis: { Disabled, Enabled }
Default: Enabled
Enables links statistics collection for the protocol.
5. Click Apply.
Section 5.4.14
Configuring the Mirrored Bits Protocol
To configure the Mirrored Bits protocol for a serial port, do the following:
1. Make sure the serial port is configured to use the Mirrored Bits protocol. For more information, refer to
Section 5.4.5, “Configuring a Serial Port”.
2. Navigate to Serial Protocols » Configure Protocols » Configure Mirrored Bits. The Mirrored Bits table
appears.