EMI and Environmental Type Tests 39
Test Description Test Levels Severity Levels
IEC 61000-4-11 Voltage Dips and
Interrupts (A. C.
Power Ports)
A.C. Power Ports 100% for 5 periods
100% for 50 periods
Signal Ports
D.C. Power Ports
IEC 61000-4-12 Damped Oscillatory
A.C. Power Ports
2.5 kV Common,
1 kV Differential
Mode @1 MHz
3
Signal PortsIEC 61000-4-16 Mains Frequency Voltage
D.C. Power Ports
30 V Continuous,
300 V for 1s
4
IEC 61000-4-17 Ripple on D.C.
Power Supply
D.C. Power Ports 10% 3
Signal Ports 2 kVAC (Fail-
Safe Relay Output)
D.C. Power Ports 1.5 kVDC
Dialiectric Strength
A.C. Power Ports 2 kVAC
Signal Ports 5 kV (Fail-Safe
Relay Output)
D.C. Power Ports
IEC 60255-5
H.V. Impulse
A.C. Power Ports
5 kV
Signal Ports 5 kV (Fail-Safe
Relay Output)
D.C. Power Ports 5 kV
Dialiectric Strength
A.C. Power Ports 5 kV
Signal Ports 2 kVAC
D.C. Power Ports 1.5 kVDC
IEC 1613/C37.90
H.V. Impulse
A.C. Power Ports 2 kVAC
Signal Ports 2.5 kV Common
Mode @1 MHz
D.C. Power Ports
Oscillatory
A.C. Power Ports
2.5 kV Common,
1 kV Differential
Mode @1 MHz
Signal Ports +/- 4 kV @ 2.5 kHz
D.C. Power Ports
A.C. Power Ports
IEC 1613/C37.90.1
Fast Transient
Earth Ground Ports
+/- 4 kV
IEEE C37.90.2 Radiated RFI Enclosure Ports 35 V/m
Enclosure Contact +/- 2kV, +/- 4kV, +/- 8kVIEC 1613/C37.90.3 ESD
Enclosure Air +/- 4kV, +/- 8kV, +/- 15kV
a