Specifications

RUGGEDCOM RSG2200
Installation Guide
Chapter 4
Technical Specifications
Fiber Optic Ethernet Port Specifications 29
Fixed Gigabit Transceivers
Order Code Connector Duplex
e
Cable Type
f
Wiring
Standard
g
Maximum
Distance
h
Isolation
i
CG01 RJ45 FDX/HDX > Category 5 TIA/EIA T568A/B 100 m (328 ft) 1.5 kV
f
Shielded or unshielded.
g
Auto-crossover and auto-polarity.
h
Typical distance. Dependent on the number of connectors and splices.
i
RMS 1 minute.
SFP Gigabit Transceivers
Order Code Connector Duplex
j
Cable Type
k
Wiring Standard
l
Maximum
Distance
Isolation
m
CG55 RJ45 FDX/HDX > Category 5 TIA/EIA T568A/B 100 m (328 ft) 1.5 kV
k
Shielded or unshielded.
l
Auto-crossover and auto-polarity.
m
RMS 1 minute.
Section 4.5
Fiber Optic Ethernet Port Specifications
The following sections list specifications of the optical transceivers used in the fiber Ethernet modules available
for the RSG2200:
NOTE
Order codes are contained within each product when assembled and configured at the factory. Refer to
the ROS User Guide for the RSG2200 for information on how to obtain the factory configuration data.
Section 4.5.1, “10FL Ethernet Optical Specifications”
Section 4.5.2, “Fast Ethernet (10/100 Mbps) Optical Specifications”
Section 4.5.3, “Gigabit Ethernet (1 Gbps) Optical Specifications”
Section 4.5.1
10FL Ethernet Optical Specifications
Order
Code
Mode
Connector
Type
Cable
Type
(µm)
Tx λ
(typ.)
(nm)
Tx min
(dBm)
Tx max
(dBm)
Rx
Sensitivity
(dBm)
Rx
Saturation
(dBm)
Distance
(typ.)
(km)
Power
Budget
(dB)
62.5/125 -16 -9 18
FL01 MM ST
50/125
850
-19.8 -12.8
-34 -11.2 2
14.2