Specifications

RUGGEDCOM RS8000
Installation Guide
Chapter 4
Technical Specifications
Power Supply Specifications 15
Technical Specifications
The following sections provide important technical specifications related to the device and available modules:
Section 4.1, “Power Supply Specifications”
Section 4.2, “Failsafe Relay Specifications”
Section 4.3, “Copper Ethernet Port Specifications”
Section 4.4, “Fiber Optic Ethernet Port Specifications”
Section 4.5, “Operating Environment”
Section 4.6, “Mechanical Specifications”
Section 4.1
Power Supply Specifications
Input Range
Power Supply Type
Minimum Maximum
Internal Fuse Rating
ab
Maximum Power
Consumption
c
12-24 VDC 10 VDC 36 VDC 6.3 A(F)
24 VDC 18 VDC 36 VDC 5 A(F)
48 VDC 36 VDC 59 VDC 3.15 A(T)
HI (125/250 VDC)
d
88 VDC 300 VDC 3.15 A(T)
HI (110/230 VAC)
d
85 VAC 265 VAC 3.15 A(T)
15 W
a
(F) denotes fast-acting fuse
b
(T) denotes time-delay fuse.
c
Power consumption varies based on configuration. 10/100Base-TX ports consume roughly 1 W less than fiber optic ports.
d
This is the same power supply for both AC and DC.
Section 4.2
Failsafe Relay Specifications
Voltage Current
30 VAC 0.3 A
30 VDC 1 A
80 VDC 0.3 A