4.3 IEC Environmental Type Tests
ENVIRONMENTAL TYPE TESTS
Test Description Test Levels Severity
Levels
IEC 60068-2-1 Cold Temperature Test Ad -40°C, 16 Hours N/A
IEC 60068-2-2 Dry Heat Test Bd +85°C, 16 Hours N/A
IEC 60068-2-30 Humidity (Damp Heat,
Cyclic)
Test Db 95% (non-condensing),
55°C , 6
cycles
N/A
IEC 60255-21-1 Vibration Tests Fc 2g @ (10 - 150) Hz Class 2
2
IEC 60255-21-2 Shock Tests Ea 30g @ 11mS Class 2
2
Notes: 1 – Only applicable to functional earth connections separated from the safety earth connection.
2 – Class 2 refers to "Measuring relays and protection equipment for which a very high security margin is required or
where the vibration levels are very high ( e.g. shipboard application and for severe transportation conditions").