Installation guide

D.C. Power ports 30V Continuous, 300V for
1s
4
IEC 61000-4-17 Ripple on D.C. Power
Supply
D.C. Power ports 10% 3
IEC 60255-5 Dielectric Strength Signal ports 2kVac (Fail-Safe Relay
output)
N/A
D.C. Power ports 1.5kVdc N/A
A.C. Power ports 2kVac N/A
IEC 60255-5 H.V. Impulse Signal ports 5kV (Fail-Safe Relay
output)
N/A
D.C. Power ports 5kV N/A
A.C. Power ports 5kV N/A
4.2 IEEE 1613 Type Tests
IEEE 1613 (C37.90.x) EMI IMMUNITYTYPE TESTS
Test Description Test Levels Severity
Levels
IEEE C37.90.3 ESD Enclosure Contact +/- 8kV N/A
Enclosure Air +/- 15kV N/A
IEEE C37.90.2 Radiated RFI Enclosure ports 35 V/m N/A
IEEE C37.90.1 Fast Transient Signal ports +/- 4kV @ 2.5kHz N/A
D.C. Power ports +/- 4kV N/A
A.C. Power ports +/- 4kV N/A
Earth ground ports
3
+/- 4kV N/A
IEEE C37.90.1 Oscillatory Signal ports 2.5kV common mode
@1MHz
N/A
D.C. Power ports 2.5kV common, 1kV diff.
mode@1MHz
N/A
A.C. Power ports 2.5kV common, 1kV diff.
mode@1MHz
N/A
IEEE C37.90 H.V. Impulse Signal ports 5kV (Fail-Safe Relay
output)
N/A
D.C. Power ports 5kV N/A
A.C. Power ports 5kV N/A
IEEE C37.90 Dielectric Strength Signal ports 2kVac N/A
D.C. Power ports 1.5kVdc N/A
A.C. Power ports 2kVac N/A
RuggedCom
®
20 RuggedMC
RMC30 Installation Guide Rev 105