Installation guide
4 Type Test Specifications
4.1 IEC 61850-3 Type Tests
IEC 61850-3 EMI TYPE TESTS
Test Description Test Levels Severity
Levels
IEC 61000-4-2 ESD Enclosure Contact +/- 8kV 4
+/- 15kV 4
Enclosure Air
IEC 61000-4-3 Radiated RFI Enclosure ports 20 V/m x
IEC 61000-4-4 Burst (Fast Transient) Signal ports +/- 4kV @ 2.5kHz x
D.C. Power ports +/- 4kV 4
A.C. Power ports +/- 4kV 4
Earth ground ports
1
+/- 4kV 4
IEC 61000-4-5 Surge Signal ports +/- 4kV line-to-earth, +/-
2kV line-to-line
4
D.C. Power ports +/- 2kV line-to-earth, +/-
1kV line-to-line
3
A.C. Power ports +/- 4kV line-to-earth, +/-
2kV line-to-line
4
IEC 61000-4-6 Induced (Conducted) RFI Signal ports 10V 3
D.C Power ports 10V 3
A.C. Power ports 10V 3
Earth ground ports
1
10V 3
IEC 61000-4-8 Magnetic Field Enclosure ports 40 A/m continuous, 1000
A/m for 1 s
N/A
IEC 61000-4-29 Voltage Dips & Interrupts D.C. Power ports 30% for 0.1s, 60% for 0.1s,
100% for 0.05s
N/A
A.C. Power ports 30% for 1 period, 60% for
50 periods
N/A
IEC 61000-4-11 100% for 5 periods, 100%
for 50 periods
2
N/A
IEC 61000-4-12 Damped Oscillatory Signal ports 2.5kV common, 1kV diff.
mode@1MHz
3
D.C. Power ports 2.5kV common, 1kV diff.
mode@1MHz
3
A.C. Power ports 2.5kV common, 1kV diff.
mode@1MHz
3
IEC 61000-4-16 Mains Frequency Voltage Signal ports 30V Continuous, 300V for
1s
4
RuggedCom
®
19 RuggedMC™
RMC30 Installation Guide Rev 105