Specifications
RUGGEDCOM RS8000
Installation Guide
Chapter 6
Certification
EMI and Environmental Type Tests 21
Test Description Test Levels Severity Levels
Signal ports 2 kVAC (Fail-Safe Relay output)
DC Power ports 1.5 kVDC
Dielectric Strength
AC Power ports 2 kVDC
Signal ports 5 kV (Fail-Safe Relay Output)
DC Power ports 5 kV
IEC 60255-5
HV Impulse
AC Power ports 5 kV
IEEE 1613 (C37.90.x) EMI Immunity Type Tests
NOTE
The RS8000 meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for
copper ports.
IEEE Test
IEEE 1613
Clause
Description Test Levels
Enclosure Contact +/- 8 kVC37.90.3 9 ESD
Enclosure Air +/- 15 kV
C37.90.2 8 Radiated RFI Enclosure ports 35 V/m
Signal ports +/- 4 kV @ 2.5 kHz
DC Power ports +/- 4 kV
AC Power ports +/- 4 kV
Fast Transient
Earth ground ports +/- 4 kV
Signal ports 2.5 kV common mode @ 1MHz
DC Power ports 2.5 kV common and
differential mode @ 1MHz
C37.90.1 7
Oscillatory
AC Power ports 2.5 kV common and
differential mode @ 1MHz
Signal ports 5 kV (Failsafe Relay)
DC Power ports 5 kV
HV Impulse
AC Power ports 5 kV
Signal ports 2 kVAC (Failsafe Relay)
DC Power ports 1.5 kVDC
C37.90 6
Dielectric
Strength
AC Power ports 2 kVAC
Environmental Type Tests
Test Description Test Levels Severity Levels
IEC 60068-2-1 Cold Temperature Test Ad -40 °C (-40 °F), 16 Hours
IEC 60068-2-2 Dry Heat Test Bd 85 °C (185 °F), 16 Hours