Specifications
Chapter 6
Certification
RUGGEDCOM RS8000
Installation Guide
20 EMI and Environmental Type Tests
Section 6.4
EMI and Environmental Type Tests
The RS8000 has passed the following EMI and environmental tests.
IEC 61850-3 Type Tests
Test Description Test Levels Severity Levels
Enclosure
Contact
+/- 8 kV 4IEC 61000-4-2 ESD
Enclosure Air +/- 15 kV 4
IEC 61000-4-3 Radiated RFI Enclosure ports 20 V/m x
Signal ports +/- 4 kV @ 2.5 kHz x
DC Power ports +/- 4 kV 4
AC Power ports +/- 4 kV 4
IEC 61000-4-4 Burst (Fast Transient)
Earth
ground ports
+/- 4 kV 4
Signal ports +/- 4 kV line-to-earth,
+/- 2 kV line-to-line
4
DC Power ports +/- 2 kV line-to-earth,
+/- 1 kV line-to-line
3
IEC 61000-4-5 Surge
AC Power ports +/- 4 kV line-to-earth,
+/- 2 kV line-to-line
4
Signal ports 10 V 3
DC Power ports 10 V 3
AC Power ports 10 V 3
IEC 61000-4-6 Induced (Conducted) RFI
Earth
ground ports
10 V 3
IEC 61000-4-8 Magnetic Field Enclosure ports 40 A/m continuous, 1000 A/m for 1 s
DC Power ports 30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
IEC 61000-4-29
30% for 1 period, 60% for 50 periods
IEC 61000-4-11
Voltage Dips and Interrupts
AC Power ports
100% for 5 periods,
100% for 50 periods
Signal ports 2.5 kV common, 1 kV
differential mode @ 1 MHz
3
DC Power ports 2.5 kV common, 1 kV
differential mode @ 1 MHz
3
IEC 61000-4-12 Damped Oscillatory
AC Power ports 2.5 kV common, 1 kV
differential mode @ 1 MHz
3
Signal ports 30 V Continuous, 300 V for 1 s 4IEC 61000-4-16 Mains Frequency Voltage
DC Power ports 30 V Continuous, 300 V for 1 s 4
IEC 61000-4-17 Ripple on DC Power Supply DC Power ports 10% 3