Technical data

Technical data
6.1 General technical data
RS 485 Repeater
Manual, 02/2011, A5E03382072-01
35
6.1.5 Specification of dielectric tests, protection class, degree of protection, and rated
voltage of S7-300
Test voltage
Proof of dielectric strength must be provided in the type test at a test voltage to IEC 61131-2:
Circuits with rated voltage V
e
to other circuits
or ground.
Test voltage
< 50 V 500 VDC
< 150 V 2500 VDC
< 250 V 4000 VDC
Protection class
Protection class I to IEC 60536, i.e., a protective conductor must be connected to the
mounting rail!
Protection against the ingress of foreign matter and water
Degree of protection IP 20 according to IEC 60529, i.e., protection against contact with
standard probes.
No protection against the ingress of water.