Technical data
Technical data
6.1 General technical data
RS 485 Repeater
34 Manual, 02/2011, A5E03382072-01
Test of mechanical environmental conditions
The table below provides important information with respect to the type and scope of the test
of ambient mechanical conditions.
Condition tested Test Standard Comment
Vibration Vibration test to IEC
60068-2-6 (sinusoidal)
Type of oscillation: Frequency sweeps with a rate of change of 1
octave/minute.
5 Hz ≤ f ≤ 9 Hz, constant amplitude 3.5 mm
9 Hz ≤ f ≤ 150Hz, constant acceleration 1 g
Duration of oscillation: 10 frequency sweeps per axis at each of three
vertically aligned axes
Shock Shock, tested to
IEC 60068-2-27
Type of shock: half-sine
Severity of shock: 15 g peak value, 11 ms duration
Direction of shock: 3 shocks in each direction (+/-) at each of three
vertically aligned axes
Climatic environmental conditions
The S7-300 may be operated on following environmental conditions:
Environmental conditions Permitted range Comments
Temperature:
horizontal mounting position:
vertical mounting position:
0°C to 60°C
0°C to 40°C
-
Relative humidity 10 % to 95 % No condensation, corresponds to relative
humidity (RH) Class 2 to IEC 61131, Part 2
Barometric pressure 1080 hPa to 795 hPa Corresponds with an altitude of -1000 m to
2000 m
SO
2
: < 0.5 ppm;
RH < 60 %, no condensation
H2
S
: < 0.1 ppm;
RH < 60 %, no condensation
Test: 10 ppm; 4 days
Test: 1 ppm; 4 days
Concentration of pollutants
ISA-S71.04 severity level G1; G2; G3 -